Function (Fct.)
Input Range
Description
2.0
CONFIG./TEST
2.1.0 OPERATION
2.1.1.0 BASIS
PARAMETER
Enter probe length to 60000 mm or 2362”
2.1.1.1 TANK
HEIGHT
As per order
Tank height.
The tank height is defined as the distance between the bottom of
the tank and the lower flange surface.
Enter 0 mm to tank height but < 24000 mm or 1063”
2.1.1.2 PROBE
LENGTH
As per order
This value has to be equal to the exact length of the probe. The
only situation for changing this value is if the probe length has
been changed.
Enter to 100 seconds
2.1.1.3 TIME
CONSTANT
5 sec.
The time constant allows filtering of possible signal fluctuations
when the product surface is turbulent.
2.1.1.4
DEAD ZONE
Enter a value
Fct.1.5.1(Detection delay) … probe length.
Warning : Critical Parameter
See „Minimal measuring distance”
Technical data of the probes
Measurements near the flange may not be precise or reliable.
Measurement may not be precise in an area less than this
recommended value, depending on the probe type.
2.1.1.5
SENSOR INFO
2.1.1.5.1 Sensor upper limit
= Probe length
Read only Menu. Upper sensor limit
2.1.1.5.2 Sensor lower limit
= 0
Read only Menu. Lower sensor limit
2.1.1.5.3 Sensor min. span
= 1 mm
Read only Menu. Sensor minimum span.
2.1.2.0 DISPLAY