22 / 44
♦
spa580en22p06
5.3.4
R
ELAY
O
UTPUT
P13: - c 0 a Relay function
FACTORY DEFAULT: 002
a
Relay operating modes
Parameters to be programmed
0
TWO POINT SWITCH
(Quantity according to
P01a
.)
The relay is energized if the measured or
calculated value exceeds the value set in
P14
The relay is de-energized if the measured
or calculated value drops below the value set
in
P15
P14, P15
At least 20 mm hysteresis must be
set between
P14
and
P15
.
P14 > P15
– normal operation
P14 < P15
– inverted operation
1
The relay is energized in case of “noECHO.”
-
2
The relay is de-energized in case of “noECHO.”
-
3
COUNTER
For open channel flow measurement. (Volume
and dimension according to P01 and P02).
It puts out a 100 ms long pulse per value
defined in P17.
P17
Pulse equivalent
(according to
P13c
)
EView2 setting:
“Device Settings”
→
“Outputs”
→
“Relay output”
→
“Relay mode.”
In de-energized state of the device the „C1” circuit is closed.
c
Dimension of P17 (ha P13a = 3)
EView2 setting:
“Device Settings”
→
“Outputs”
→
“Relay output”
→
“Relay
parameters”
→
“Pulse constants unit.”
Metric
US
0
m
3
ft
3
1
liter
gallon (BR)
2
liter
gallon (US)
P14: - - - - Relay parameter – Operating value
FACTORY DEFAULT: 0
EView2 setting:
“Device Settings”
→
“Outputs”
→
“Relay output”
→
“Relay parameters”
→
“Energized value.”
P15: - - - - Relay parameter – Releasing value
FACTORY DEFAULT: 0
EView2 setting:
“Device Settings”
→
“Outputs”
→
“Relay output”
→
“Relay parameters”
→
“De-Energized value.”
P17: - - - - Relay parameter – Pulse rate see P13a= 3
FACTORY DEFAULT: 0
EView2 setting:
“Device Settings”
→
“Outputs”
→
“Relay output”
→
“Relay parameters”
→
“Pulse constant.”