P71: - - - - Distance of the of Measuring Window
P72 - - - - Amplitude of the selected echo [dB] <0
P73:
Position of the selected echo (time) : (ms)
[
ms
]
P74:
Signal to Noise Ratio
Ratio
Measurement conditions
Over 70
Excellent
Between 70 and 50
Good
Under 50
Unreliable
P75: - - - - Blocking Distance
This parameter gives information about the actual close-end blocking distance (provided automatic blocking was selected in P05)
5.4.8.
T
EST PARAMETERS
P96: - - - - Checksum
P97: - - - - Software code (Read only parameter)
P98: - - - - Hardware code (Read only parameter)
P99: dcba Access lock by secret code
The purpose of this feature is to provide protection against accidental programming of parameters or by a person. not entitled. The secret code can be
any value other than 0000. Setting a secret code will automatically be activated when the EasyTREK is returned to the Measurement Mode. In order to
program locked device the secret code should be entered first in P99. Thus for entering a new code or erasing the old one the knowledge of the
previous code is necessary.