EasyTREK Compact Ultrasonic Level Transmitters
9
1.3 Relay Output
P13: - - - a
Relay function
a
Relay function
Also set:
0
DIFFERENTIAL LEVEL CONTROL
(Hysteresis control)
Relay is energised if the measured or calculated
value exceeds the value set in P14
Relay is de-energised if the measured or calculated
value descends under the value set in P15
Relay
Level
P14
P15
Time
Energised:
De-energised:
P14, P15
There is a need to set
(in level min 20mm)
hysteresis between
P14 and P15
1
Relay is energised in case of Echo Loss
-
2
Relay is de-energised in case of Echo Loss
-
3
COUNTER
Used for open channel flow metering.
A 140 msec pulse is generated every 1, 10, 100,
1.000 or 10.000 m
3
according to P16.
P16= 0: 1m
3
P16= 1: 10 m
3
P16= 2: 100 m
3
P16= 3: 1.000 m
3
P16= 4: 10.000 m
3
FACTORY DEFAULT: 2
P14: …
Relay parameter – Setpoint value
P15: …
Relay parameter – Setpoint value
P16: …
Relay parameter – Pulse rate see P13(3)
FACTORY DEFAULT: P14=0, P15=0, P16=0