Nittan EVCA-P Instruction Manual Download Page 13

 

DW1500110  Rev.K1 

Sep  18  2015 

13

 

 

 

6.4 

Tamper resistance feature 

The EVA-UB series of smoke/heat detector mounting bases have a tamper- resist feature that works in conjunction 
with the detectors. When this feature is enabled, the detectors cannot be removed from the base without the use of a 
small hexagonal wrench. To avoid unauthorized removal of the detector, turn the locking screw in the mounting base 

counterclockwise until the screw extends out about 4 mm (3/16 in.) from the rim of the base, as shown in Figure 11. 
 

 
 

 
 
 
 
 
 
 
 
 
 
 

Figure 11: Position of the locking screw to lock the detector

 

Note:

 If the detector is installed on a high ceiling where a tool (ladder, etc.) is needed, it is not recommended to use the 

locking screw. 

Section 7 

 TESTING 

Notes:

 

 Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily 

be out of service. 

 Disable the system to prevent unwanted alarms. 

 All sensors must be tested after installation and periodically thereafter. 

 Testing methods must satisfy the Authority Having Jurisdiction (AHJ). 

 When carrying out site testing of the  detector, the control panel must 

be set to “One Man Walk Test” mode 

prior to the test. 

Sensors offer maximum performance when tested  and maintained in compliance with NFPA 72. The sensor  may be 

tested in the following ways: 

A.  For the smoke detector testing (Go / No-Go) 

1. 

To  test  the  optical  detector, introduce  a  certain  amount  of  aerosol  into  the  detector

s  head,  using

 

Solo  330 

Aerosol  Dispenser  with  Solo  A3  Smoke  Detector  Tester  (No  Climb  Products  Ltd.).  Please  follow  the 

manufacturer’s recommendations on their use. 

 

2. 

Check that the detector gives an alarm condition within 15 seconds. Check the red LED indicator lights on the 

EVCA-P 

smoke detector. If the red LED fails to light, check the power to the detector and the wiring in the 

detector base. 

3. 

After  the  detector  has  given the  alarm  condition, the detector  automatically is  reset  by the  control  panel. It 

may be necessary to allow a short time to elapse before resetting the detector, to allow any residual aerosol 
from the test to disperse. 

4. 

Detectors that fail these tests should be cleaned as described under MAINTENANCE Section and retested. If 

the detectors still fail these tests they should be returned for repair. 

5. 

Before proceeding to the next detector, ensure that the detector previously tested does not re-operate due to 
the presence of residual aerosol. 

 

 

Summary of Contents for EVCA-P

Page 1: ...ow the requirements for the installation of the products in accordance with the Specifications Otherwise it may cause malfunction Note Do not install the product in any location where oil dust iron po...

Page 2: ...nsect screen therefore reducing the ingress of insects and airborne contaminants The chamber is designed so that the light emitted by the LED is not directed to the photodiode The LED pulses every 8 s...

Page 3: ...imension of EVCA P Section 4 TERMINALS The EVCA P smoke detector has three terminal connections and the terminals are configured as follows Terminal Description 1 Zone negative in 3 Zone positive in o...

Page 4: ...please consider the following items Otherwise the detector might not provide optimum performance Indoor use only Place the detector away from a ventilation fan or the air outlet of air conditioner at...

Page 5: ...nals a dirty sensor trouble to the control panel when it reaches the preset limit The dirty sensor trouble indicates the detector is in need of servicing 6 2 2 Spacing of Smoke Detectors The recommend...

Page 6: ...ing as shown in Figure 2 Figure 2 Smoke detector layout accounting for stratification 6 2 4 Partitions It is recommended that the distance between smoke detectors should not exceed a nominal spacing o...

Page 7: ...the bottom of the joists Figure 3 Smoke detector spacing solid joist construction side view Figure 4 Smoke detector spacing solid joist construction plan view Note Joists less than 10 cm 4 in deep ar...

Page 8: ...W H is greater than 0 4 Smoke detectors shall be located on the bottom of each beam if either the ratio of beam depth D to ceiling height H D H is less than 0 1 or the ratio of beam spacing W to ceili...

Page 9: ...nd of the ceiling Additional detectors if required must be located based on the horizontal projection of the ceiling and the type of ceiling construction For a ceiling slope of less than 30 degrees al...

Page 10: ...g sure the wiring does not obstruct mounting of the detector head Push the detector into the mounting base while turning it clockwise until the detector locks into place Use a small hexagonal wrench t...

Page 11: ...th is 1km Refer to the instruction manual of EVA ZMU SCI Zone Module for connection to NFU 7000 series Use cable AWG12 20 for wiring Do not connect different gauge cables at one terminal in order to p...

Page 12: ...15 12 Figure 10 Correct and incorrect wiring method For system monitoring For terminals 1 and 6 do not use looped wire under terminals Break wire run to provide monitoring of connections CAUTION Corre...

Page 13: ...control panel must be set to One Man Walk Test mode prior to the test Sensors offer maximum performance when tested and maintained in compliance with NFPA 72 The sensor may be tested in the following...

Page 14: ...of residual aerosol Section 8 MAINTENANCE Notes Before cleaning notify the proper authorities that the system is undergoing maintenance and therefore the system will temporarily be out of service Dis...

Page 15: ...rm Characteristics 6VDC in series with 375R between Terminal 3 and Terminal 1 6 at 25 C UL Ambient Installation Temperature 0 C to 49 C 32 F to 120 F Operating Temperature 10 C to 55 C 14 F to 131 F S...

Page 16: ...e this had been paid And the warranty period is three 3 years from the shipment from Nittan s factory 9 3 Notwithstanding anything to the contrary in this warranty terms Nittan shall not be liable to...

Reviews: