DW1401990  Rev.K2 

Dec 18, 2019 

Compatibility Requirement 

To ensure proper operation, the module shall be connected to UL listed 

control panel NFU-7000 series.   

 

Before Installing 

Disconnect  power  to  the  control  panel  before  installing  the  module.  If 

the  module  is  installed  in  an  existing  operational  system,  inform  the 

operators and local authorities that the system will be temporarily out 

of service.   

 

Mounting 

Mount the module directly to 4’’ square electrical box (UL Listed). 

Secure the module to the electrical box, as shown in Figure 3.   

 

Main unit

Outer cover EVA

Electrical box

Tapping screw

Pan head screw

 

Figure 3 

 

Setting 

Address Setting 

Use EVA-AD2 Programmer for setting the address of the module prior 

to  installation.  EVA-ZMU-SCI  has  an  address  given  at  random  from 

factory.  Connect  the  Programmer  with  the  address  setting  port  to 

change  the  address  to  any  of  1-254  (dec),  with  reference  to  the 

instruction  manual  of  EVA-AD2  Programmer.  The  address  can  be  set 

regardless of whether power supply from the control panel is turned on 

or  off.  During  setting  address,  the  module  does  not  respond  to  the 

control panel.   

Set the address of module according to Job data. 

 

 

 

Subtype Setting 

Set  the  subtype  depending  on  the  wiring  configuration  as  below.  The 

subtype is to be set through the Configurator for the control panel. 

Sub 

type   

Input 

  Method 

Open 

-

circuit 

Detection 

Short 

-

circuit 

Detection 

Class 

Interrupt 

Normally 

Open 

Yes 

No 

Class B 

Disabled 

Enabled 

Class A 

Disabled 

Enabled 

Normally 

Open 

Yes 

Yes 

Class B 

Disabled 

Enabled 

Class A 

Disabled 

Enabled 

When interrupt is enabled, it allows a high priority

 

communication to 

the control panel. The consumption current increases with this setting. 

 

Note : Applicable subtype setting differs depending on control panels. 

Subtype 1 to 8 can be used with the control panel complying with UL864 

9th edition. 

Subtype 5 to 8 can be used with the control panel complying with UL864 

10th edition. 

Please contact Nittan customer service for any required details. 

 

Compatible  Two  wire  detector  for  use  with  EVA-ZMU-SCI  with  Zone 

Identifier A: 

 

Detector 

Model 

Compatibility 

ID 

Detector 

Type 

Base 

Model 

Base 

ID 

Max. 

No. of 

Detectors 

EVCA-P 

Photoelectric 

EVA 

-UB4 

EVA 

-UB4-6 

20 

Operating voltage range 12 to 18VDC 

 

 

 

 

 

 

 