Compatibility Requirement
To ensure proper operation, the module shall be connected to UL listed
control panel NFU-7000 series.
Before Installing
Disconnect power to the control panel before installing the module. If
the module is installed in an existing operational system, inform the
operators and local authorities that the system will be temporarily out
of service.
Mounting
Mount the module directly to 4’’ square electrical box (UL Listed).
Secure the module to the electrical box, as shown in Figure 3.
Main unit
Outer cover EVA
Electrical box
Tapping screw
Pan head screw
Figure 3
Setting
・
Address Setting
Use EVA-AD2 Programmer for setting the address of the module prior
to installation. EVA-ZMU-SCI has an address given at random from
factory. Connect the Programmer with the address setting port to
change the address to any of 1-254 (dec), with reference to the
instruction manual of EVA-AD2 Programmer. The address can be set
regardless of whether power supply from the control panel is turned on
or off. During setting address, the module does not respond to the
control panel.
Set the address of module according to Job data.
・
Subtype Setting
Set the subtype depending on the wiring configuration as below. The
subtype is to be set through the Configurator for the control panel.
Sub
type
Input
Method
Open
-
circuit
Detection
Short
-
circuit
Detection
Class
Interrupt
1
Normally
Open
Yes
No
Class B
Disabled
2
Enabled
3
Class A
Disabled
4
Enabled
5
Normally
Open
Yes
Yes
Class B
Disabled
6
Enabled
7
Class A
Disabled
8
Enabled
When interrupt is enabled, it allows a high priority
communication to
the control panel. The consumption current increases with this setting.
Note : Applicable subtype setting differs depending on control panels.
Subtype 1 to 8 can be used with the control panel complying with UL864
9th edition.
Subtype 5 to 8 can be used with the control panel complying with UL864
10th edition.
Please contact Nittan customer service for any required details.
Compatible Two wire detector for use with EVA-ZMU-SCI with Zone
Identifier A:
Detector
Model
Compatibility
ID
Detector
Type
Base
Model
Base
ID
Max.
No. of
Detectors
EVCA-P
A
Photoelectric
EVA
-UB4
EVA
-UB4-6
A
20
Operating voltage range 12 to 18VDC