4)

 

After  the  module  is  brought  into  the  active  condition,  reset  the 

module. It may be necessary to allow a short time to elapse before 

the module is reset. 

Confirm  that  the module  goes  back  to  the  initial  status  after the 

active  status  is  reset.  (In  the  normal  status,  no  voltage  is output 

between S+ and S- (or between R+ and R-). 

5)

 

Short between terminal Lin+ (Lout+) and Lin- (Lout-), and the SCI 

LED (yellow) is illuminated. The short circuit isolator isolates the 

devices connected after the short-circuited area, which makes these 

devices have no response. Upon removal of the short condition, the 

area is automatically connected to go back to the normal standby 

status, and the SCI LED (yellow) turns off. 

   

FOR WARRANTY SERVICE, RETURN TO: 

 

OVERSEAS BUSINESS DIVISION, NITTAN COMPANY, LIMITED

 

1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN 

 

http://www.nittan.com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specifications 

Applied Voltage 

SLC    Rated Range    20 to 38VDC 

I

±

      Rated Range

 

16 to 30VDC 

SLC Current Consumption 

Standby 0.8mA 

Activated 3.6mA 

SLC Line Impedance 

Up to 50 ohms 

Relay

(±

I

 

Switching capacity 

DC 30V/2A 

Number of NAC Circuits 

1 x Class A or 1 x Class B 

NAC Circuit Rating 

16 to 30VDC, 2A (max) 

NAC Line Impedance 

Up to 50 ohms 

EOL Device   

RE-10k (10k ohms, 1/4W)     

Class B only 

SCI on Resistance 

0.2 ohms

 

(max) 

SCI Fault Detection Threshold 

10V (min) 

SCI Isolation Current 

22mA (max) 

Visual Indicator (Status LED) 

Polling LED 

GREEN

 

Output LED 

RED

 

SCI LED 

YELLOW

 

Ambient Installation 

Temperature   

 

0

  to

 

49

(32°F to 120°F) 

Storage Temperature   

-20

  to 60

(-4°F to 140°F) 

Max Relative Humidity 

Up to 93

  RH

non-condensing 

Environment 

Indoor dry use only 

Maximum quantity per loop 

127 units 

Terminal 

Screw

 

AWG12 to 22 

Address setting 

EVA-AD2 Address Programmer 

Dimensions 

124mm H x 124mm W x 34.5mm D 

(4.882’’ H x 4.882’’ W x 1.358’’ D) 

(Mount  to  a  4’’  square  by  2

’’  deep 

box) 

Weight 

Approximately 167g (5.9oz) 

Conformity 

UL864 

 

 

 

 

 

 

 