Section 4 - INSTALLATION

In normal use, the 

EV-DP

sensor will be installed at ceiling level. Pass

the field wiring through the cable hole in the centre and from the rear

of the base.  Offer up and affix the base to the ceiling or conduit

fitting with screws via the base mounting holes.  Connect the field

wiring to the base terminals, as detailed on page 9 making sure the

wiring does not obstruct fitting of the detector head.  Fit the sensor

head by inserting it into the base and turning clockwise until the notch

in the detector rim aligns with base locking screw.  The OMNIVIEW™

360º alarm indicator permits visibility from any angle.

Note: The address must be set before the sensor is fitted into place

Fit the plastic dust cover supplied over the sensor to keep out dust etc,

until the system is commissioned.  If the dust cover is not fitted and the

environment is slightly dusty, such as when building work is being

completed, for example, problems of false alarms are likely to occur

after commissioning unless cleaning of the sensor is undertaken.  At

commissioning, the dust cover should be removed and discarded.

NOTE: THE PLASTIC DUST COVER MUST BE REMOVED FROM THE

SENSOR IN ORDER FOR THE SENSOR TO FUNCTION CORRECTLY.

Section 5 - MAINTENANCE 

AND CLEANING

Maintenance:

The 

EV-DP

sensor is a high quality product engineered for reliability.

If proper preventative maintenance is not carried out, there is a

likelihood of malfunction, including false alarms.

Servicing:

Servicing of the system should be carried out in accordance with 

the requirements of BS 5839 Part 1, Fire Detection and Alarm 

Systems for Buildings: Code of Practice for System Design, 

Installation and Servicing.

Summary of Contents for EV-DP

Page 1: ...e www nittan co uk E mail sales nittan co uk Ref No NISM EV DP 03 Date 16 04 09 Issue 3 Evolution EV DP Dual Wavelength photoelectric sensor instruction manual EV DP Analogue Addressable Dual Waveleng...

Page 2: ...EV UV are all elegantly designed low profile fire sensors which are aesthetically pleasing thus enabling them to blend unobtrusively into modern working environments The evolution analogue addressable...

Page 3: ...ng terminals provide a switched current sink function which operates when the detector goes into alarm condition suitable for the operation of an auxiliary function such as a remote indicator Terminal...

Page 4: ...ss must be set before the sensor is fitted into place Fit the plastic dust cover supplied over the sensor to keep out dust etc until the system is commissioned If the dust cover is not fitted and the...

Page 5: ...l It may be advisable to ensure that such cleaning is conducted regularly in the future iv Ensure no equipment which may generate combustion products has been installed in the vicinity of the detector...

Page 6: ...proceeding to the next sensor ensure that the sensor previously tested does not re operate due to the presence of residual smoke Functional Tests The functional test checks the sensor operation These...

Page 7: ...ve Humidity of up to 95 measured at 50 C non condensing Section 8 EMC Installation The installation shall be in accordance with the regulations either of the approval body for an approved system or ot...

Page 8: ...ncrement the address to be programmed by one 1 and prompt for the next sensor to be fitted If no detector is fitted the programmer will report No Unit Found Comm Error 1 Fit a new sensor and press OK...

Page 9: ...olution EV DP analogue addressable photoelectric sensor instruction manual Auxiliary terminal RIL current limited to 3mA Base control is not current limited as the auxiliary equipment provides the lim...

Page 10: ...ct your local city office or your household waste disposal service Section 13 ROHS COMPLIANCE STATEMENT RoHS compliant and lead free This product complies with the RoHS Restriction of Hazardous Substa...

Reviews: