EV-2I1O (-EU) Installation instructions   

 

IIS-EV-2I1O (-EU) Issue 4 04/03/2019 

Address Setting 

Loosen the Allen key screw to open the access door in the front, using the 1.5mm Allen 
key provided. It is possible to configure the address setting and change the setting of DIP 
switch or jumper pin (refer to Figure 1). 

Use EV-AD2-EXT to set the address of the EV-2I1O (-EU). The factory default address of 1 is 
given to the module. Connect the EV-AD2-EXT to the address setting port with the Micro 
USB cable for the programmer and change the address to any of 1-254, with reference to 
the instruction manual of EV-AD2-EXT programmer.  (Note that the number of available 
addresses can be less depending on a control panel model.) The address can be set 
regardless of whether power supply from the control panel is turned on or off. 

Address setting is possible even after connecting the module to the Loop. 

DIP Switch Operation 

With DIP switch 1, it is possible to select normal mode or failsafe mode (refer to Table 1 
and Figure 1). The DIP switch 2 can change the input setting (normally open/ normally 
closed). 

If the loop power supply is off, the relay is activated in the failsafe mode. Refer to Table 2 
for the relay position in each condition in the normal/failsafe mode.  

DIP switch  

Position 

Function 

ON 

Failsafe mode 

OFF 

Normal mode  

ON 

Input circuit 1: Normally closed 

OFF 

Input circuit 1 & 2: Normally open 

Table 1

 

Table 2 

LED Operation 

Five LEDs are visible through the translucent access door of the enclosure (refer to Figure 2 
and Table 3). 

Polling LED: flashes green during polling from the control panel. 

Input LED: illuminates red to indicate that an input is activated. 

Output LED: illuminates red when the output relay is on after receiving a command from 
the control panel. 

Fault LED: illuminates yellow when a fault condition, i.e. an open or short circuit in the input 
circuit, or relay stuck fault is detected in the output circuit. 

SCI LED: illuminates yellow when a short circuit is detected in the loop and the short circuit 
isolator (SCI) is activated. 

 

Dimensions 

          

 

      

 

End of Life Disposal 

Like all electronic equipment, at the end of its working life this unit should not be disposed 
of in a refuse bin. All Nittan products since 2005 have been marked with the WEEE Logo in 
compliance with European Directive 2012/19/EU and Nittan Europe Limited is a member 
of a WEEE Compliance Scheme. Contact [email protected] for a copy of our WEEE 
Compliance Policy. 
 
 
 
 
 

Condition 

Relay Normal

    

mode 

Relay Failsafe mode 

Loop power Off 

Off 

On 

Standby 

Off 

Off 

Alarm 

On 

On 

Figure 6 – EV-2I1O 

Figure 7 – EV-2I1O-EU 

mm (in) 

mm (in) 

Page 7 

Page 2 

www.acornfiresecurity.com

www.acornfiresecurity.com