Before test, press “Alarm Transfer Isolation” switch, “Hydrant Isolation” switch and if necessary, 

“Maintenance” switch to maintenance side. 

 

A. When every 5 zones are tested. (normally test is carried out in this manner). 

  Press “Fire Test” switch to test side. 

 

  Set “Zone Selection Tens Digit” switch to “1~10” and set “Zone Selection Ones Digit” switch 

to ”1”, then the 1

st

 “Zone” alarm indicator turns on and at the same time, “Alarm Delay” 

indicator turns on. 

          After passing specified alarm delay time (20 seconds), the common “Fire” indicator turns on 

and panel alarm sounder and zone alarm bell start to sound.     

   When “Panel Alarm Silence” switch is pressed downward, panel alarm sounder silences and 

“Zone Alarm Silence” switch is pressed downward, zone alarm bell is silenced but when 

“Maintenance” switch is pressed to maintenance side, all zone alarm bells do not sound. 

However, “Alarm Delay” light continues to turn on. 

 

  When “Zone Selection Ones Digit” switch is set to “2”, the 2nd “Zone” alarm indicator turns 

on and panel alarm sounder starts to re-sound. At this moment, the 1

st

 “Zone” alarm 

indicator remains turning on. The rest of remaining zones can be set to alarm condition one 

by one, but after the 1

st

 zone alarm, fire test for the 2

nd

 zone onward is carried out under 

alarm delay cancelled condition. 

 

  After completion of the 5

th

 zone test, press “Reset” switch downward to conduct reset 

operation, then set “Zone Selection Ones Digit” switch to “6” and carry out the test for the 

6

th

 zone to the 10

th

 zone in the same manner.   

   

  When the 11

th

 zone test is carried out, set “Zone Selection Tens Digit” switch to “11~20” and 

set “Zone Selection Ones Digit” switch to “1”. 

Note: Do not test over 5 zones at the same time since this may cause some trouble. 

 

B. When every one zone is tested. 

Press downward “Fire Test” switch and “Reset” switch and configure “Zone Selection Tens 

Digit” switch to “1~10”. When you operate “Zone Selection Ones Digit” switch from 1, fire 

test can be carried out per zone. When “Auto Reset” switch is pressed to “RESET” side, 

alarm delay function is cancelled but “Alarm Delay Confirmation” light turns on. 

 

C. When a specific selected zone is tested. 

Configure the specified zone by “Zone Selection Tens Digit” switch and “Zone Selection Ones 

Digit” switch and press “Fire Test” switch downward. “Zone” alarm indicator and “Alarm 

Delay” indicator turn on and after pre-determined delay time (20 seconds), “Fire” indicator 

turns on and alarm sounder sounds. 

Note: When reset operation is made by “Reset” switch, CPU is cleared once.   

 

        CPU needs rise time of 2~3 seconds. 

 

 

 

 

Please confirm “Circuit Voltage” indicator is turning on when “Battery Test” switch is pressed 

downward. When the light is turning on, standby battery to be used at power cut is in normal 

condition. When “Circuit Voltage” light turns off (at below 20.4V) and alarm buzzer sounds, 

inspect charge circuit and battery. Please pay attention that alarm buzzer can not sound if 

standby battery is nearly flat. Also, at battery test when AC power is supplied, “AC Power 

Supply” light remains turning on. 

 

 

 

 

 

 

4. Various Testing Methods 

Fire Test 

 

 

Standby Battery Test 

 

 

Summary of Contents for 1PM3-nLA

Page 1: ...unds by operation of manual alarm station or by receipt of alarm signal from other zone Highly reliable design LED is used for all indicators Solid state by avoiding relays to the utmost and high func...

Page 2: ...3 Condition of Monitoring Time and Fire Alarm Time 7 4 Various Testing Methods 9 5 Symptom of Fuse Meltdown 10 6 Block Diagram 11 7 Connection Examples of Various Signal Transfer 12 8 Standard Specifi...

Page 3: ...be lost Please secure effective space to enable switch operation in case of emergency otherwise this may cause fire and electrification and also equipment function may be lost Switch operation shall...

Page 4: ...late Hanger CUD label Zone Alarm Indicator When a fire breaks out it indicates fire starting place Also when line break occurs at detector line it indicates line break zone by flickering Difference in...

Page 5: ...of control panel circuit voltage When circuit voltage becomes lower than about 20 4V the light turns off 4 Switch operation indicator If any one of switches is not at normal position the light red fl...

Page 6: ...nance tone When the maintenance switch is operated the panel buzzer sounds with a small click sound once in 10 seconds After that if pressing and holding the Panel Alarm Silence Switch the panel buzze...

Page 7: ...ncy PA silences At this moment switch operation light 4 starts to flicker 25 Fire test switch This switch is used to measure alarm delay time at fire test When the switch is pressed to test side switc...

Page 8: ...zone selection tens digit switch of operating board is ON only for the 1st switch These switches are already configured upon factory shipment Also these switches alarm delay OFF switch individual alar...

Page 9: ...alarm station so fire indicator turns on immediately Panel alarm sounder and zone alarm bell start to sound 3 Condition of Monitoring Time and Fire Alarm Time The following is monitoring condition at...

Page 10: ...or equipped with confirmation light is turning on its confirmation light In this case check environmental condition of detector surroundings This will help clarify causes of unwanted alarms and formul...

Page 11: ...out the test for the 6th zone to the 10th zone in the same manner When the 11th zone test is carried out set Zone Selection Tens Digit switch to 11 20 and set Zone Selection Ones Digit switch to 1 Not...

Page 12: ...ire Alarm Receipt Start Time and if it remains between 15 20 seconds it is normal Note Please measure the time 2 3 seconds after Reset switch operation When you measure alarm delay time set Alarm Tran...

Page 13: ...11 6 Block Diagram...

Page 14: ...ormation receiving device GB rfa GC GA J S IC I I1 In IB C T BZ IC I I1 In IB C T annunciator control panel side 1 signal transfer to security company etc 1 1 in case of constant open route type 1 2 i...

Page 15: ...3F B B B B B3 B1 BC B2 rbx15 rbx1 rbb rbx2 rbx3 Q8 S9 rba PC 03157 B4 B15 CN14 1 CN14 2 CN14 3 CN14 4 CN14 5 CN15 1 CN15 2 7 Connection Examples of Various Signal Transfer Please bundle up all connec...

Page 16: ...t function time Flickers when alarm delay cancel switch S29 is ON The light does not turn on at individual alarm delay cancellation time Other alarm indicator Red LED x 3 turn on when external alarm i...

Page 17: ...450 x 100 1060 x 450 x 100 Note Zone bell connection quantity A quantity when motor bell DC24V 10mA is connected P type Class 1 Control PanelAccessory List 1PM3 nLA Item Name Quantity 5 10LA 15 40LA...

Page 18: ...nd function 6 months Overall inspection 12 months Wiring Overall inspection 12 months These regular inspections and report to Fire Service Authority shall be carried out by qualified personnel such as...

Page 19: ......