13
Test
B
W508 owns a test mode procedure to check all output relevant devices
(alarm panels, external buzzers, links to alarm devices, and system
failure contact) in a very comfortable manner.
T
o reach this “test mode” an authorized person has to “switch off” system.
After that authorized person keep pushing rotary encoder S2 and switch
on system at the same time. System starts in “test mode 1” and display is
showing as follow
1
st
Stage Alarm is activated as long as S2 is pushed again. The 1
st
Stage
Alarm indication on BW508CONN is on. Display is showing as follow
A
fter a.m. test in “test mode 1” is done, user has to turn S2 clockwise to
reach “test mode 2”. Display is showing as follow
2
nd
Stage Alarm is activated as long as S2 is pushed again. The 2
nd
Stage Alarm indication on BW508CONN is on. Display is showing as
follow