nilan MULTILINK Installation Instructions Manual Download Page 15

Troubleshooting

Communication

Troubleshooting communication errors

If a communication error occurs, check the following:

1. Check that the gateway and the ventilation units are powered
2. Check whether the Data+ and the Data- wires have been switched
3. Check that each ventilation unit has its own unique Modbus address in accordance with the template

provided

4. Check that there is activity on LED1 at Ethernet plug 2 on the gateway (the activity must be regular)
5. Check that the gateway is connected to the internet (can you access the internet with a computer

via the Ethernet cable for the gateway)

6. Check that all ventilation units are grounded correctly.

Modbus network

Data+ and Data- refer to ground in each individual control system, which, through the control system,

is connected to protective earthing (PE). The voltage between Data+/Data- and the reference (PE) is

called the common mode voltage. The common mode voltage / the potential difference between

ground points must not exceed 5Vrms AC and DC.

At the gateway, ground connected up to PE ground and. wired to each junction box, but as a rule are not

connected to the control, as this has its own PE ground connection. Check the voltage difference from

the grounded shield to the frame of the steering. If it exceeds 5Vrms, check if the controller is

connected to PE ground via the supply cable. If the voltage is not lowered below 5Vrms via the ground

wire, the frame wire is connected from the cable between the connection box and the controller. Now

the screen and the power line will provide the potential equalization between the control and the

gateway. The frame and screen are brought together at the gateway and in the junction box in order to

handle a slightly larger ground loop current.

Nilan MultiLink (English)

 BY NILAN

15

Summary of Contents for MULTILINK

Page 1: ...INSTALLATION INSTRUCTIONS NILAN MULTILINK BY NILAN Nilan MultiLink English Version 1 10 29 08 2019...

Page 2: ...ecification 7 Example Gateway and two ventilation units 8 Example Gateway and two ventilation units in separate buildings 8 Wiring 9 Installation Setup 10 Setting of Modbus addresses 10 Gateway inform...

Page 3: ...ructions The following symbols are used to direct the attention of the user to different levels of warnings ATTENTION Important information CAUTION Warning General warning Definitions HW Hardware elec...

Page 4: ...lan MultiLink please contact Lodam support www lodam com Phone 45 73 42 37 37 ATTENTION Please note that there is a charge for support unless a fault or an error has been made by Bitzer It is therefor...

Page 5: ...mponents that may be included in the MultiLink system Gateway basic kit consisting of 1 Gateway 1 Power supply 1 Installation plug For mounting on DIN rail in electrical switchboard cabinet and for co...

Page 6: ...stalled in the mounting box connection via SIM card Insulated repeater To be used if the units do not have the same ground potential For mounting on DIN rail in electrical switchboard cabinet Insulate...

Page 7: ...use a star connection or similar cabling There can be up to 10 ventilation units per gateway Bitzer has junction boxes so conductors and wires can be connected correctly The cable from the junction bo...

Page 8: ...gateway Example Gateway and two ventilation units in separate buildings The example below shows an installation with two units in separate buildings It shows the gateway installed in a mounting box D...

Page 9: ...end terminal in the two outer units and not in gateway D 1 D 1 D 1 D 1 G N D G N D D 1 D 1 G N D D 0 D 0 D 0 D 0 G N D G N D D 0 D 0 G N D Data Data Internet L L N N P E P E L N P E 2 Modbus PE sk rm...

Page 10: ...dbus PE sk rm L N DC 1 DC 3 PWR D 2 D 1 GND 5 GATEWAY PSU 12V Anl g 1 Modbus adresse 41 Anl g 2 Modbus adresse 42 Anl g 3 Modbus adresse 43 Anl g 4 Modbus adresse 44 2 Terminering 120 Ohm D 1 D 1 G N...

Page 11: ...of the Nilan MultiLink system Example of information noted down Designation Gateway ID Nyvej 2 00 60 e0 6c 98 8f Designation Modbus address Ground floor to the left 41 Ground floor to the right 42 1st...

Page 12: ...e If you have ordered the gateway with a mounting box install the Modbus connection in DO for one line For two lines install the other line in DI and remove the end terminal D 1 D 1 D 1 D 1 G N D G N...

Page 13: ...f the attached aerial does not reach it is possible to connect an external aerial which will provide a better signal Connection to the unit For most products Modbus connections to Nilan s units take p...

Page 14: ...2 Unit 3 Unit 4 Unit 5 Unit 6 Unit 7 Unit 8 Unit 9 Unit 10 Designation Gateway ID MAC address Designation Modbus address Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Unit 6 Unit 7 Unit 8 Unit 9 Unit 10 Designa...

Page 15: ...tective earthing PE The voltage between Data Data and the reference PE is called the common mode voltage The common mode voltage the potential difference between ground points must not exceed 5Vrms AC...

Page 16: ...ey Tlf 353 0 87 9798361 maurice nilan ie www nilanireland ie Document no M20_MultiLink_GB Nilan A S disclaims all liability for potential errors and omissions in printed instructions or for loss or da...

Reviews: