Connecting two fire dampers
You can connect two fire dampers. When connecting two fire dampers, the contact functions must be connected in series as outlined
below. Note that the two extra wires from dampers (S3 and S5) are not used. Connect the supply voltage from Neutral and relay 5 in a
parallel circuit.
Mount junctions in an external junction box (not supplied by Nilan)
Connect up S1-S6 to Nilan’s fire automation box as shown under “Connecting fire dampers”
Fire damper 1 Fire damper 2
M
1
S4
2
1
2
1
M20
S2
S1
S6
M
1
S4
M20
S2
S1/S6
S2
S4
S1
S6
Relay 5
Neutral
Relay 5
Neutral