Lux range:
Choose between two lux ranges
Normal lux range
0 -1023 lux
High lux range
0 - 10360 lux
Table 1.
Sensitivity:
It is possible to change the sensitivity of the detector or to disconnect
individually for Segment A, B or C.
Tabel 1.
Walk test:
To check that the detector detects correctly, it is possible to perform a walk
test. In walk test the LED will indicate which segment is being activated. Seg-
ment A is indicated via red LED, segment B is indicated via green LED and
segment C is indicated via blue LED.
Fig. 5.
The detector must be set in walk test mode to do this.
Fig. 10.
Walk test can only be activated via IR remote control 41-934 (accessory).
Operation & maintenance
Dirt affects the operation of the detector and the detector’s lens must
therefore be kept clean. Use a damp cloth for cleaning. Use water mixed
with normal cleaning agent. Avoid pressing hard on the lens. If the lens or
other parts of the detector are defective, it must be replaced.
Technical data
Input:
Supply voltage .........................................via the DALI bus
Power consumption ................................ 7 mA
Performance:
Lux range ................................................0 - 1023 lux
0 - 10360 lux
Detection area ........................................(3-120°) 360°
Sensitivity ................................................4 settings
Protection class (gasket is mounted) ......... IP 54
Colour ....................................................RAL 9010 (white)
Ambient temperature ..............................-5°C ... +50°C
Performance - type no. 41-742 and 41-743:
Detection range for body movement
(at installation height of 3 m) .................... 450 m²
Range for small movements
(at 2.5 m installation height) ..................... 9 m²
Installation height ..................................... 2 – 3.4 m
Performance - type no. 41-745:
Detection range for body movements ..... Ø16-32
Installation height ..................................... 4 – 8 m
Certifications:
CE in accordance with............................. EN 60669-2-1
Standards:
DALI .......................................................IEC 62386-101
IEC 62386-103
IEC 62386-303
IEC 62386-304
Accessories
IR remote control....................................41-934
LED status
Overview of LED status:
Status
Indication
Unlock
The green LED lights when the detector is being
programmed and is ready for configuration via the
IR remote control 41-934 (accessory).
Lock
The green LED turns off. The detector is locked
and the most recently programmed
changes are saved.
Walk test
Sektor A
The red LED will flash when activity is detected
in segment A.
Fig. 10.
Walk test
Sektor B
The green LED will flash when activity is detected
in segment B.
Fig. 10.
Walk test
Sektor C
The blue LED will flash when activity is detected
in segment C.
Fig. 10.
IR remote control
41-934 (accessory)
Each time the detector receives a correct signal
from the IR remote control, the detector will
acknowledge by briefly turning off the green LED if
the detector is being programmed.
Environment
This product and/or the batteries provided cannot be deposited in
non-recyclable waste. Take your discarded product to a recognised
collection point. Just like producers and importers, you too play an
important role in the promotion of sorting, recycling and reuse of
discarded electrical and electronic equipment. To finance the rubbish
collection and waste treatment, the government levies recycling charges
in certain cases (included in the price of this product).
EMBALLAGES
CARTONS ET PAPIER
À TRIER