Module ID
The SI-Interbus module displays the module ID code in Pr
MM.001
, this module ID code
can be used to identify the module variant.
14.2
Firmware version
Pr
MM.002
displays the SI-Interbus firmware version in the form ww.xx.yy.zz.
14.3
Interbus data format
The SI-Interbus data format is specified as ‘NNPP’, where ‘NN’ specifies the non-cyclic
data mode, and ‘PP’ specifies the number of cyclic process data words as shown in the
following table.
MM.001
SI-Interbus Module ID
Minimum
0
Maximum
999
Default
None
Units
None
Type
16 Bit Volatile
Update Rate
Power-up write
Display format
None
Decimal Places
0
Coding
RO, ND, NC, PT, BU
Pr MM.001
SI-Interbus variant
404
500 kBd
414
2 MBd
MM.002
SI-Interbus Firmware Version
Minimum
0
(Display: 0.00.00.00)
Maximum
99999999
(Display: 99.99.99.99)
Default
0
(Display: 0.00.00.00)
Units
None
Type
32 Bit Volatile
Update Rate
Power-up write
Display format
Version
Decimal Places
0
Coding
RO, ND, NC, PT
MM.005
SI-Interbus Data Format
Minimum
0
Maximum
309
Default
4
Units
None
Type
16 Bit User Save
Update Rate
Background read
Display format
None
Decimal Places
0
Coding
RW
Pr MM.005
NN
PP
Non-cyclic Mode
Cyclic Words
1 to 10
0
1 to 10
None
1 to 10
100 to 109
1
0 to 9
CT Single Word
0 to 9
200 to 209
2
0 to 6
PPO 4 Word
0 to 6
300 to 309
3
0 to 9
PCP
0 to 9