5
Maintenance and service guide - LSPX-FLSPX ZONE
21 - Ex tb – LSES-FLSES ZONE
22 - Ex tc
5725 en - 2020.02 / c
1 - RECEPTION
This manual or its condensed version is to be given to the end user. In the event of this notice not being translated into the language of the country in which
the motor is used, the distributor is responsible for its translation and for distributing it to end users.
Products to which this manual applies may not be commissioned before the machinery in which they are installed has been declared to conform to the Directives that apply to it.
This equipment and its accessories or associated equipment must be installed by a professional, who is liable for ensuring compliance with all installation rules, decrees,
orders, laws, directives, application memos, standards (where explosive atmospheres are involved, standard IEC-EN 60079-14 as a minimum), regulations, good trade
practices and any other documents relating to the installation site. The professional is also liable for ensuring compliance with the values indicated on the motor information
plate(s), instruction manuals, installation and maintenance manuals and any other document provided by the manufacturer.
Constructions Electriques de Beaucourt (CEB) and LEROY-SOMER cannot be held liable for non-compliance with all or part of the above or with any part of
this manual.
On receipt of your motor, check that it has not suffered any damage in transit.
If there are obvious signs of damage, contact the carrier (you may able to claim on their insurance) and after a visual check, turn the motor by hand to detect
any malfunction.
1.1 - Identification and marking
Check that the information shown on the nameplate is compatible with the explosive atmosphere that is present, the utilisation zone and the ambient and surface
temperatures.
Mains supply nameplate
Variable speed nameplate
Quadratic torque variable speed nameplate
Definition of symbols used on nameplates:
Legal mark of equipment compliance
with the requirements of European Directives.
Special ATEX marking
IECEx
:
II 2D or II 3D
: ATEX/IECEx marking
Ex tb or tc
: Protection mode “dust” envelope
III B or III C
: Equipment group
T125°C
: Maximum surface temperature
Db or Dc
: “dust” EPL level
0080
: Notified organisation INERIS (as II 2D)
INERIS ... X
: ATEX attestation no.
IECEx INE...
: IECEx certificate no.
Motor symbols:
MOT 3 ~
: Three-phase A.C. motor
FLSES
: Motor type
280
: Frame size
M
: Housing symbol
4
: 4 poles
B3
: Operating position
No.
: Serial number
2017
: Year of manufacture
IM
: Operating position symbol
°C
: Maximum ambient temperature
Ins. cl.
: Winding insulation class
S
: Standard operating duty
%
: Operating duty
d/h
: Number of starts per hour
SF
: Duty factor
kg
: Weight
DE
: Drive end bearing
NDE
: Non drive end bearing
g
: Quantity of grease to be added per bearing
at each re-lubrication (in g)
h
: Interval in hours between re-lubrication
IP
: Index of protection
IK
: Impact resistance index
m
: Maximum operating altitude
V
: Supply voltage
Hz
: Supply frequency
min
-1
: Rated speed of rotation
kW
: Rated power
A
: Rated current
cos
j
: Power factor
%
: Efficiency at 4/4 load
D
: Delta coupling
: Star coupling
POLYREX EM 103
: Grease part number for
bearings
Insulated bearing : NDE
: Insulated bearing NDE
side
Manufactured by CEB
: Equipment manufacturer
EAC Ex
: Equipment for explosive atmospheres
certified for Eurasia
cURus
: Class F insulation
E068554
for USA and Canada
A
: Vibration level code
H
: Balancing mode code
NY
: Starting requirements code
279 E
: Plate reference
Zone
ATEX/IECEx
marking
Protection
mode
marking
Maximum
surface
temperature
E.P.L.
level
Index of
protection
min
21
II 2 D
Ex tb IIIC
T125°
Db
IP 65
22
II 3 D
Ex tc IIIB
T125°
Dc
IP 55
INSTALLATION AND MAINTENANCE - LSPX-FLSPX ZONE 21 - Ex tb – LSES-FLSES ZONE 22 - Ex tc
IE %
: Efficiency level and efficiency,
at rated load and voltage
2/4
: Efficiency at 2/4 load
3/4
: Efficiency at 3/4 load
Inverter settings PWM
: Characteristics for setting the PWM drive to allow temperature class of motor to be met
Motor performance valid for 400V - 50Hz at inverter input
: Motor performance for a voltage of 400V - 50 Hz at the
drive input
Duty S9
: Performances given for S9 duty
Min.Fsw
: Minimum switching frequency of the drive in kHz
Nmax
: Admissible maximum motor speed in rpm
PTC 140°C
: PTC sensor type - temperature limit = 140°C
IOL
: Admissible over-current = 1.5 x rated current
tOL
: Maximum period during which over-current can occur (in secs)
tcool
: Minimum duration during which the motor must be at the max of its rated current between
2 over-current events (in secs)
Quadratic torque
: Type of torque: quadratic
IVIC
: Pulse voltage insulation class code