Table 5-6 Maximum permissible continuous output current @ 50 °C (122 °F)
Model
Normal Duty
Heavy Duty
Maximum permissible continuous output current (A)
for the following switching frequencies
Maximum permissible continuous output current (A)
for the following switching frequencies
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz
200 V
05200250
30
29.7
25.2
21.6
25
23
19.8
17.3
06200330
50
49
38
30
33
29
24.6
06200440
58
56
49
38
30.2
44
41
36
29
24.6
400 V
05400270
25.5
23.6
20.4
15.6
12.3
24
23.5
21.6
18.6
16.2
12.7
10
05400300
25.5
23.6
15.9
12.3
24
21.9
19.2
13.8
10.5
06400350
38
37
28
21.4
35
32
27
21
16.5
06400420
48
43
36.5
27.4
21.4
42
38
32
27
21
16.5
06400470
63
58
52
43
37
28
21.4
47
42
38
32
27
21
16.5
575 V
05500030
3.9
3.0
05500040
6.1
4.0
05500069
10
6.9
06500100
12
10
06500150
17
13.4
15
14
10.3
06500190
22
17.8
13.4
19
14
10.3
06500230
27
23.5
17.8
15
23
21.6
19
14
11.5
06500290
34
28.2
23.5
18
15
29
27.3
22
19
14
11.6
06500350
43.0
41.7
36.1
28
23.7
18
15
35
31.2
27.3
21.8
19
14
11.6
55