Unidrive M Modular Installation Guide
25
Issue Number: 2
5 Mechanical Installation
This chapter describes all the mechanical details required to install the
drive. The drive is intended to be installed in an enclosure. Key features
of this chapter include:
•
Surface and through-panel mounting
•
Remote mounting of control master pod
•
Enclosure sizing and layout
•
Solutions Module installation
•
Terminal location and torque settings
•
Docking the Unidrive M size 9/10 D and Rectifier
5.1 Safety information
5.2 Planning the installation
The following considerations must be made when planning the installation:
5.2.1 Access
Access must be restricted to authorized personnel only. Safety
regulations which apply at the place of use must be complied with. The
IP (Ingress Protection) rating of the drive is installation dependent.
5.2.2 Environmental protection
The drive must be protected from:
•
moisture, including dripping water or spraying water and
condensation. An anti-condensation heater may be required, which
must be switched off when the drive is running.
•
contamination with electrically conductive material
•
contamination with any form of dust which may restrict the fan, or
impair airflow over various components
•
temperature beyond the specified operating and storage ranges
•
corrosive gasses
During installation it is recommended that the vents on the drive are
covered to prevent debris (e.g. wire off-cuts) from entering the drive.
5.2.3 Cooling
The heat produced by the drive must be removed without its specified
operating temperature being exceeded. Note that a sealed enclosure
gives much reduced cooling compared with a ventilated one, and may
need to be larger and/or use internal air circulating fans.
For further information, please refer to section 5.6.4
5.2.4 Electrical safety
The installation must be safe under normal and fault conditions.
Electrical installation instructions are given in Chapter 6
5.2.5 Fire protection
The drive enclosure is not classified as a fire enclosure. A separate fire
enclosure must be provided.
For installation in the USA, a NEMA 12 enclosure is suitable.
For installation outside the USA, the following (based on IEC 62109-1,
standard for PV inverters) is recommended.
Enclosure can be metal and/or polymeric, polymer must meet
requirements which can be summarized for larger enclosures as using
materials meeting at least UL 94 class 5VB at the point of minimum
thickness.
Air filter assemblies to be at least class V-2.
The location and size of the bottom shall cover the area shown in Figure
5-1. Any part of the side which is within the area traced out by the 5°
angle is also considered to be part of the bottom of the fire enclosure.
Figure 5-1 Fire enclosure bottom layout
The bottom, including the part of the side considered to be part of the
bottom, must be designed to prevent escape of burning material - either
by having no openings or by having a baffle construction. This means
that openings for cables etc. must be sealed with materials meeting the
5VB requirement, or else have a baffle above. See Figure 5-2 for
acceptable baffle construction. This does not apply for mounting in an
enclosed electrical operating area (restricted access) with concrete floor.
Figure 5-2 Fire enclosure baffle construction
Follow the instructions
The mechanical and electrical installation instructions must
be adhered to. Any questions or doubt should be referred to
the supplier of the equipment. It is the responsibility of the
owner or user to ensure that the installation of the drive and
any external option unit, and the way in which they are
operated and maintained, comply with the requirements of
the Health and Safety at Work Act in the United Kingdom or
applicable legislation and regulations and codes of practice in
the country in which the equipment is used.
Competence of the installer
The drive must be installed by professional assemblers who
are familiar with the requirements for safety and EMC. The
assembler is responsible for ensuring that the end product or
system complies with all the relevant laws in the country
where it is to be used.
Many of the drives in this product range weigh in excess of 15
kg (33 lb). Use appropriate safeguards when lifting these
models.
Enclosure
The drive is intended to be mounted in an enclosure which
prevents access except by trained and authorized
personnel, and which prevents the ingress of contamination.
It is designed for use in an environment classified as
pollution degree 2 in accordance with IEC 60664-1. This
means that only dry, non-conducting contamination is
acceptable.
WARNING
WARNING
WARNING
WARNING
NOTE
Drive
5
o
5
o
N o t l e s s
t h a n 2 X
B a f f l e p l a t e s ( m a y b e
a b o v e o r b e l o w b o t t o m
o f e n c l o s u r e )
X
B o t t o m
o f f i r e
e n c l o s u r e
Not less
than 2
times ‘X’
Baffle plates (may be above or
below bottom of enclosure)
Bottom of fire enclosure
X