Holding Register 2:
Max Speed [RPM]
This register can be used to set the max speed of the fan.
Allowed values
= [Min Speed, Default Value]
Default value
= table below
7/7T
7/7
7/9 8/7T 9/7 8/9T 225/240 9/9 10/8 10/10 12/9 12/12 15/11 15/15
1.05kW
1-Phase
3000 2000 2000 2000 2000 2000
2000
2000 2000 2000
-
-
-
-
2.1kW
1-Phase
-
-
-
-
-
-
-
2000 2000 2000 1600 1600
-
-
2.65kW
3-Phase
-
-
-
-
-
-
-
2000 2000 2000 1600 1600
-
-
4kW
3-Phase
-
-
-
-
-
-
-
-
-
-
-
*
*
*
Holding Register 7:
Max Current [mA]
This register can be used to reduce the max motor current.
Allowed values
= [1, Default value]
Default value
= table below
7/7T
7/7
7/9 8/7T 9/7 8/9T 225/240 9/9 10/8 10/10 12/9 12/12 15/11 15/15
1.05kW
1-Phase
6000 4500 4500 4500 4500 4500
4500
4500 5500 5500
-
-
-
-
2.1kW
1-Phase
-
-
-
-
-
-
-
8300 8300 8300 8300 8300
-
-
2.65kW
3-Phase
-
-
-
-
-
-
-
8000 8000 8000 8000 8000
-
-
4kW
3-Phase
-
-
-
-
-
-
-
-
-
-
-
*
*
*
Holding Register 16:
Speed Threshold Low [RPM]
This register can be used to set the speed threshold low.
The register is active when the
register 46
is set to the value 3.
Allowed values
= [0, Speed Threshold High]
Default value
= 0
Holding Register 21:
Fixed Speed setting [RPM]
This register can be used to set the speed in
Fixed Speed Control Mode
.
The register is active when the Input Type
Holding Register 34
is set to the value 2.
Allowed values
= [Min Speed, Max Speed]
Default value
= 0
Holding Register 30:
Asynchronous Slip. [%]
This register can be used to set the slip of an emulated ACIM motor.
The register is active when the Input Type Holding Register is set to the value 9.
Allowed values
= [0, 100]
Default value
= 0
Holding Register 31:
PID Positive/Negative [Adim]
This register can be used to invert the feedback behavior of the PID.
Allowed values
= 0 and 1
Default value
= 0
*
The value is under development.
*
The value is under development.
Although the value of the Max Current can be set at any value being lower than the original default one, it is not
recommended using a value that is 0.3 times below the default one.