NICOR, Inc. 2200 Midtown Place NE, Albuquerque, NM 87107 P: 800.821.6283 F: 800.892.8393 www.nicorlighting.com July 22, 2021 9:58 AM
EXPRESS LIMITED WARRANTY
Subject to the exclusions contained below, NICOR Inc. (NICOR) warrants that all NICOR LED branded Solid State Lighting products made by NICOR to be free from defects in materials and workmanship, under normal consumer usage
for a period of 3 years from date of purchase. This limited warranty is a consumer’s exclusive remedy, and applies only to new products purchased and used by consumers in the United States or Canada, which are accompanied by
this written warranty.
This limited warranty extends only to the first consumer purchaser, and is not transferable. A consumer wishing to invoke the terms of this warranty must first obtain a RGA number within 30 days of discovery of the defect, and
return the product to NICOR for inspection. Once verified to be covered by this limited warranty, NICOR will, at its discretion, repair, replace or refund the purchase price of any product that does not conform to this limited warranty.
This limited warranty covers only defects in material and workmanship associated with normal installation and intended use of the product.
THIS LIMITED WARRANTY DOES NOT COVER THE FOLLOWING:
• Defects or damages resulting from improper operation, storage, misuse or abuse, accident or neglect;
• Defects or damages resulting from improper service, testing, adjustment, installation, maintenance, alteration, connection to out-of-specification electrical service, corrosive or damp environments, or connection to incompatible
equipment or devices (e.g., connecting non-dimmable lighting products to dimmers);
• Damage which occurs in transit; and
• Labor or other charges or expenses associated with the removal, repair, or re-installation of defective or replacement products.
ANY IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE SHALL BE LIMITED TO THE DURATION OF THIS LIMITED WARRANTY,
OTHERWISE THE REPAIR, REPLACEMENT OR REFUND AS PROVIDED UNDER THIS EXPRESS LIMITED WARRANTY IS THE EXCLUSIVE REMEDY OF THE CONSUMER, AND IS PROVIDED IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED. IN NO EVENT SHALL NICOR BE LIABLE, WHETHER IN CONTRACT OR IN TORT (INCLUDING NEGLIGENCE) FOR DAMAGES IN EXCESS OF THE PURCHASE PRICE OF THE PRODUCT, OR FOR ANY INDIRECT, INCIDENTAL, SPECIAL OR
CONSEQUENTIAL DAMAGES OF ANY KIND, OR LOSS OF REVENUE OR PROFITS, LOSS OF BUSINESS OR OTHER FINANCIAL LOSS ARISING OUT OF OR IN CONNECTION WITH THE ABILITY OR INABLILITY TO USE THE PRODUCT TO THE FULL
EXTENT THESE DAMAGES MAY BE DISCLAIMED BY LAW.
Copyright 2016, NICOR, Inc.
Revised November, 2016
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interfer-
ence that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
EMB4001UNV**
INSTALLATION INSTRUCTIONS
TEST SWITCH OPERATIONS
Manual Diagnostic Mode:
Under the normal charging mode, after the battery is
charged for 12 hours or fully charged, long press the test
button for 3 seconds and hold it to enter the manual test
mode. Release the button to exit the manual diagnostic
mode.
Enable / Disable Self-Diagnostic Test System:
With AC power supplied to the unit:
To disable the Self-Diagnostic Test mode, press the button
twice in two seconds, then press the button longer than
2 seconds but less than 5 seconds, then press the button
twice in succession. The indicator light will flash 5 times (1
sec. interval)
To enable the Self-Diagnostic Test System, repeat the op-
eration, the indicator light will flash 3 times (1 sec. interval).
Enter Sleep Mode:
Under EM mode, press the test button for 3 seconds,
EMB400 will enter Sleep Mode (used for storage and
transportation). Awaken the unit by connecting to AC
power.
REMOTE CONTROL OPERATION:
Under the normal charging mode, press the "ON" button
of the remote control to enter the manual diagnostic test
mode, and press the "OFF" button of the remote control to
exit the manual diagnostic mode
LED Indicator Status
EMB400 Status/Mode
ON solid green
• System OK / AC OK
OFF
• System fault
• Battery voltage too low
• LED fixture may have failed
Flashing Green
1s on/1s off (continual)
• Battery not detected,
• Check battery connections
Flashing Green
0.1s on/5s off (continual)
• Working in emergency
mode
Slow Flashing Green
5s on/5s off (continual)
• Self diagnostic test:
discharge time is <90min
• LED fixture is open circuit
• System overload
Flashing Green
5s on/5s off (5 times)
• Self diagnostic test diabled
Flashing Green
1s on/1s off (3 times)
• Self diagnostic test enabled
TEST SWITCH INDICATOR STATUS