NICOR EML6 Installation Instructions Download Page 2

NICOR, Inc.   2200 Midtown Place NE, Albuquerque, NM 87107 P: 800.821.6283 F: 800.892.8393   www.nicorlighting.com  December 10, 2019 11:29 AM

EML6 

LED Emergency Light

INSTALLATION INSTRUCTIONS

Model: EML61UNVWH

2.1

2

2.1

Mounting Instructions

Back Mounting

•  Drill or knock out appropriate knockouts on the backplate to fit junction box mounting points and the center 

3/4” knockout for the input wire leads.

•  Remove backing from self adhesive junction box gasket and adhere to back plate. 
•  Feed the power supply through the knockout. Run the wires through the mounting bracket as seen in ”Figure 3 - 

Back Mount.” 

•  Ensure that power is off, then connect the power supply, 120 or 277 Vac, to the appropriate input wires, using the 

provided wire nuts, according to ”Figure 1 - Wiring Diagram.” The unused wire must be capped off using a wire 
nut. 

•  Snap the fixture onto the backplate. 
•  Using the provided (2) mounting screws, secure the fixture the the junction box.
•  Connect the battery to the LED board. Secure the faceplate to the fixture. Do not over tighten the screws.

Figure 3 - 

Back Mount

NOTE

Battery Testing: Allow 24 hours of charging before testing.
•  Push In TEST Button - LED display will switch to battery power and remain lit 
•  Release TEST Button - LED display will switch back to AC power

Gasket

Reviews: