NICOR, Inc. 2200 Midtown Place NE, Albuquerque, NM 87107 P: 800.821.6283 F: 800.892.8393 www.nicorlighting.com December 10, 2019 11:29 AM
EML6
LED Emergency Light
INSTALLATION INSTRUCTIONS
Model: EML61UNVWH
2.1
2
2.1
Mounting Instructions
Back Mounting
• Drill or knock out appropriate knockouts on the backplate to fit junction box mounting points and the center
3/4” knockout for the input wire leads.
• Remove backing from self adhesive junction box gasket and adhere to back plate.
• Feed the power supply through the knockout. Run the wires through the mounting bracket as seen in ”Figure 3 -
Back Mount.”
• Ensure that power is off, then connect the power supply, 120 or 277 Vac, to the appropriate input wires, using the
provided wire nuts, according to ”Figure 1 - Wiring Diagram.” The unused wire must be capped off using a wire
nut.
• Snap the fixture onto the backplate.
• Using the provided (2) mounting screws, secure the fixture the the junction box.
• Connect the battery to the LED board. Secure the faceplate to the fixture. Do not over tighten the screws.
Figure 3 -
Back Mount
NOTE
Battery Testing: Allow 24 hours of charging before testing.
• Push In TEST Button - LED display will switch to battery power and remain lit
• Release TEST Button - LED display will switch back to AC power