insufficient. In this case, interrupt the procedure by pressing “P1” on the
control unit: then tension the chain by tightening nut and repeat the pro-
cedure from the beginning.

This procedure can be repeated at any time: for example after a mechanical
travel stop has been moved on the guide.

The control unit has a number of optional functions to enable the user to add
specific  functionalities  to  the  automation,  thus  personalising  the  product
according to special needs.

10

– AUTOMATION OPERATION ADJUSTMENT

To personalise operation of the automation, a number of functions can be
enabled  or  disabled,  also  with  the  option  for  modifications  to  settings  as
required. The functions are:

• AUTOMATIC CLOSURE

. When this function is enabled, at the end of the

Opening

manoeuvre command by the user, the control unit automatically clos-

es the door again after a set time interval.

• MOVEMENT SPEED

. This function enables entry of the required speed of

the automation implemented to move the door.

• SENSITIVITY TO OBSTACLES

. During a manoeuvre, if an obstacle acciden-

tally stops door movement (a gust of wind, a vehicle, person etc.) this function
promptly detects the increase in motor stress to contract the obstacle and acti-
vates immediate and brief inversion of movement.

• PRESSURE DISCHARGE

. At the end of the Closing manoeuvre, after the

door has closed completely, the motor continues to “push” the door for a brief
interval, to ensure perfect closure. Immediately afterwards, this function acti-
vates a very brief inversion of movement, to reduce excessive pressure exerted
by the motor on the door.

The values of these functions can be set according to personal requirements
using  the  following  procedure  with  a  transmitter  that  has  at  least  one  key
already memorised on the control unit.

Note 

– During this procedure, each time a key is pressed the courtesy light illu-

minates briefly.

01.

Press and hold the keys “

T1

” and “

T2

” simultaneously on the transmitter

for at least 

5 seconds

, after which release.

The two leds (green and red) on the Control unit flash to indicate entry to
function programming mode 

(the leds continue to flash throughout the

procedure)

.

02.

Press and hold a transmitter key (already memorised on that of the control
unit) for at least 

1 second

(

the green Led emits one flash

).

03.

Then select one of the four functions available and on the transmitter press
the key associated with the function for at least 

1 second

(the green Led

emits one flash)

:

• Automatic closure

= (press key “

T1

”)

• Movement speed

= (press key “

T2

”)

• Sensitivity to obstacles

= (press key “

T3

”)

• Pressure discharge

(= press key “

T4

”)

04.

Lastly, refer to

Table 4

, select the required value in correspondence with

the selected function and on the transmitter press the key associated with
the selected value for at least 

1 second

(the green and red Leds emit one

confirmation flash)

.

ADJUSTMENTS AND OTHER 

OPTIONAL FUNCTIONS

STEP 9

A WARNINGS for programming:

• Always read the procedure 

first and then perform

the operations in the cor-

rect sequence. without leaving more than 10 seconds between releasing one
key and pressing the next.

• In this manual the transmitter keys are identified by means of numbers. To
check the correspondence of 

numbers

and the transmitter 

keys

see 

fig. 46

.

9.1

– MEMORISATION OF TRANSMITTER MOD. FLO4R-S

To enable control of the automation with the transmitter, the keys must be
memorised in the control unit memory.
Memorisation enables the association of each key with the required command,
selecting from the following:

1

Step-Step

: Corresponds to the sequence 

... Open - Stop – Close - Stop

...

The first command activates Opening; the next, with the leaf moving, acti-

vates Stop; the third activates 

Closure

; the fourth with the door moving acti-

vates 

Stop

and so on…

2

Step-Open

: Corresponds to the sequence 

... Open - Stop – Close -

Open ...

The first command activates Opening; the next, with the leaf moving,

activates 

Stop

; the third activates 

Closure

; the fourth with the door moving acti-

vates 

Open

and so on...

3

Partial open

: corresponds to a brief opening of the door. This command

is only enabled if the door is completely closed.

4

Courtesy light

... On - Off - On ...

A single procedure memorises 

a single key

of the transmitter; this can be

memorised  both  on  the  present  control  unit  and  on  control  units  of  other
automations. The control unit memory can memorise up to 150 keys.
For each key to be memorised, repeat the following procedure.

01.

Select which transmitter 

key

is to be memorised (for example:

Key T3

).

02.

Decide on the 

command

(from those listed below) to be associated with

the selected key (for example:

Command “

2

).

03.

Press “

P1

” (on the Control unit) the same number of times as the selected

command number

(in the example “

2

”, i.e. twice)

and check that the green

led emits the same number of quick flashes (repeated at regular intervals).

04.

(within 10 seconds) Press and hold the transmitter key to be memorised
for at least 2 seconds 

(in the example, key T3)

.

If the memorisation procedure is successful, the green led emits 3 long flashes
(= 

memorisation OK

). 

Note – Before the 10 second interval elapses, the key of

a NEW transmitter with the same command can be memorised (useful, for
example, when several transmitters need to be memorised on the same control
unit).
Otherwise wait until the green led turns off (= procedure completed) and for the
red led to resume flashing at regular intervals.

9.2

– MEMORISING  THE  DOOR 

“OPENING”

AND 

“CLOSING”

TRAVEL LIMIT POSITIONS

The 

“Closing”

limit position (

B

- fig. 47

) corresponds to the maximum door

closing

position and the 

“Opening”

limit position (

A

- fig. 47

) to maximum

opening

.

In this installation phase, the control unit must memorise the maximum door

“Closing”

and 

“Opening”

positions and the configuration of the STOP input,

using the following procedure:

CAUTION! 

– The following operations must be performed using exclu-

sively key P1 on the gearmotor control unit.

01.

Ensure that the drive carriage is engaged.

02.

Press and hold “

P1

” on the Control unit (for approx. 5 seconds) until the

red

light illuminates, then release.

03.

At this point the control unit independently starts 3 consecutive manoeuvres

(Closing – Opening – Closing) 

to automatically memorise the two travel lim-

it positions. 

Note

– During the 3 manoeuvres, the courtesy light flashes.

Caution! 

– During the 3 manoeuvres, if a safety devices is activated

or P1 is pressed, the control unit interrupts and automatically can-
cels the entire procedure. In this case the entire procedure needs to
be repeated.

04.

Lastly, use the transmitter key 

T1

activate 3 or 4 complete Opening and

Closing manoeuvres (these manoeuvres are required for the control unit to
memorise the 

force

values required to move the door at all points of travel).

Caution! 

– These manoeuvres must not be interrupted; should this

occur, the entire procedure must be repeated.

CAUTION! 

– During the position search process, if the chain on the pinion

pulley of the motor emits a rhythmic noise, indicating that tensioning is

PROGRAMMING THE AUTOMATION

E

N

Summary of Contents for Shel50Kit

Page 1: ...so FR Instructions et avertissements pour l installation et l utilisation ES Instrucciones y advertencias para la instalaci n y el uso DE Installierungs und Gebrauchsanleitungen und Hinweise PL Instru...

Page 2: ......

Page 3: ...EMBLY AND CONNECTION STEP 5 5 1 Installing the automation components 4 5 2 Fixing the automation to the wall ceiling and door 4 STEP 6 System device installation and connection 5 POWER SUPPLY CONNECTI...

Page 4: ...this occur disconnect the power supply immediately and contact a Nice service centre Use of the automation in these conditions constitutes a hazard never place automation components near to sources o...

Page 5: ...th the technical specifications of the gearmotor Ensure that the area for mounting the gearmotor and guide is compatible with the overall dimensions of the automation to be installed Then ensure that...

Page 6: ...the length of distance B consider ing the constraints of values A and E fig 3 If the door is UP AND OVER establish the length of distance B con sidering the constraints of value F fig 4 Note If values...

Page 7: ...se a connection layout in series as shown in the example in fig 41 C to connect a series of devices with constant resistance 8 2 K use a parallel connection layout positioning the resistance 8 2K on t...

Page 8: ...itter the keys must be memorised in the control unit memory Memorisation enables the association of each key with the required command selecting from the following 1 Step Step Corresponds to the seque...

Page 9: ...ng key P1 press the transmitter key to be deleted if the control unit recognises this operation the green led emits a short flash after which the P1 key and transmitter key can be released TABLE 4 AUT...

Page 10: ...utoma tion and not visible from the latter it must be fitted with a lockout facility to pre vent inadvertent or unauthorised connection Note The disconnect devices are not supplied with the product AU...

Page 11: ...claration correspond to those of the last revision available of the official document deposited at the registered offices of Nice S p a before printing of this manual The text herein has been re edite...

Page 12: ...ode Self learning of door opening and closing positions and calculation of deceleration and partial open points Use in particularly acid or saline No potentially explosive atmospheres Protection class...

Page 13: ...legislation locally in force In the event of malfunctions or power failures While you are waiting for the technician to come or for the power to be restored if your system is not equipped with buffer...

Page 14: ...IONAAL PROJECTING DEBORDANTE D BORDANTE DESBORDANTE AUSFAHREND WYSTAJ CA BUITEN DE GEVEL DRAAIEND NON PROJECTING NON DE BORDANTE NON D BORDANTE NO DESBORDANTE NICHT AU SFAHREND NIEWYSTAJ CA BINNEN DE...

Page 15: ...9 6 7 8 a b c d l e f h m g g...

Page 16: ...V3 5 x 15 10 A A A B A C 11 13 14 15 16 12 V6 x 30 R06 open aperta ouverte abierta ge ffnet otwarta open b a V8 x 45...

Page 17: ...19 17 a 17 b 20 22 18 M8 R8 x 24 V8 x 45 21 23 M6 V6 x 18...

Page 18: ...24 V6 x 14 M6 B 4 400 mm 25 90 25 a 26 29 30 28...

Page 19: ...31 32 33 34 35 1 2 1 2 3 4 TX RX 1 2 3 4 5 36 Input STOP 0 VOLT LINE 24 Vcc Input STEP BY STEP Input PHOTO 1 2 3 4 5 1 1 2 1 2 3 4 2 3 4 5 TX RX 1 2 1 2 3 4 TX RX 37 1 2 3 4 5 38...

Page 20: ...1 2 3 4 5 40 1 2 3 4 5 41 1 2 3 4 5 42 1 2 3 4 5 NA NC 43 44 45 P1 Green Led Led verde Led verte Led verde gr ne Led Zielona dioda Groene led Red Led Led rosso Led rouge Led rojo rote Led Czerwona di...

Reviews: