PROGRAMMING
6
6
PROGRAMMING
There are 3 buttons on the control unit:
f
,
g
and
h
(“
Figure
”) which can be used both to command
the control unit during the testing phase and to programme the
available functions.
The
i
button is not used.
19
The available programmable functions are grouped into
two levels
and their operating status is signalled by eight LEDs “
L1 ... L8
”
located on the control unit (LED lit = function enabled; LED off =
function disabled).
6.1 USING THE PROGRAMMING BUTTONS
f
Button for commanding the gate opening
Selection button during the programming phase.
g
Button used to stop a manoeuvre
If pressed for more than 5 seconds, it allows for entering the
programming mode.
h
Button for commanding the gate’s closure
Selection button during the programming phase.
i
–
Button not used.
6.2 LEVEL 1 PROGRAMMING (ON-OFF)
All Level 1 functions are factory-set to “
OFF
” and can be modified at any time. To check the various functions, refer to “
6.2.1 Level 1 programming procedure
m
The user has maximum 10 seconds to press the buttons consecutively during the programming procedure,
after which time the procedure terminates automatically and memorises the changes made up to then.
To perform Level 1 programming:
1.
press and hold the
g
button until LED “
L1
” starts flashing
2.
release the
g
button when LED “
L1
” starts flashing
3.
press the
f
or
h
button to move the flashing LED to the LED associated with the function to be modified
4.
press the
g
button to change the status of the function:
–
short flash =
OFF
–
long flash =
ON
5.
wait 10 seconds (maximum time) to exit the programming mode.
l
To set other functions to “ON” or “OFF”, while the procedure is running, repeat points 2 and 3 during the phase
itself.
Table 6
LEVEL 1 FUNCTIONS (ON-OFF)
LED
Function
Description
L1
Automatic closing
Function ENABLED:
after an opening manoeuvre there is a pause (equal to the set pause time), after which
the control unit automatically starts a closing manoeuvre. The pause time is set by default to 30 seconds.
Function NOT ENABLED:
the system works in “semi-automatic” mode.
L2
Close after photo
Function ENABLED:
if the photocells intervene during the opening or closing manoeuvre, the pause time
drops to 5 seconds regardless of the set “pause time”. With “automatic closing” disabled, if the photocells
intervene during the opening or closing manoeuvre, the “automatic closing” activates with the set “pause time”.
L3
Always Close
Function ENABLED:
in the event of a blackout, even of short duration, 10 seconds after the electricity is
restored the control unit detects that the gate is open and automatically starts a closing manoeuvre, preceded
by 5 seconds of pre-flashing.
Function DISABLED:
when the electricity is restored, the gate remains in the same position.
L4
Stand-by all
Function ENABLED:
1 minute after the manoeuvre is completed, the control unit will turn off the “Bluebus”
output (connected devices) and all the LEDs, with the exception of the Bluebus LED, which will flash at a
slower speed. When the control unit receives a command, it restores normal operation (with a short delay).
This function is used to reduce consumption – an important aspect when the unit is powered by batteries or
photovoltaic panels.