Nibe HPAC S40 Installer Manual Download Page 21

Pipe connections

GENERAL

Pipe installation must be carried out in accordance with
applicable regulations. HPAC S40 can only operate up to a
return temperature of about 50 °C and an outgoing temper-
ature of about 65 °C from the heat pump.

The fluid in the building's distribution system is the same
as in the surface soil/rock collector, if no other heat ex-
changer is connected.

PIPE CONNECTION, THE BUILDING’S CLIMATE

SYSTEM

Connect the heat pump to HPAC S40 and, where applicable,
hot water heating.

Pipe connections are made at the bottom and top of
HPAC S40. All required safety devices, shut-off valves (in-
stalled as close to the cooling module as possible), and
particle filter (supplied with the heat pump) are to be fitted
in such a way that HPAC S40 is also protected.

If HPAC S40 is connected to a system with thermostats on
all convectors, a bypass valve must be fitted or a number
of thermostats must be removed to ensure sufficient flow.

Pipe connection

3

1

1

3

3

1

1

3

-EQ1

XL1

XL2

XL6

XL9

XL8

XL17

XL7

XL16

PIPE CONNECTION, COLLECTOR SIDE

The length of the collector hose varies depending on the
rock /surface soil conditions and on the climate system.

Ensure the collector hose rises constantly towards the heat
pump to avoid air pockets. If this is not possible, airvents
should be used.

All the system's pipes must be condensation insulated ex-
cept the pipes to the water heater.

Because the temperature of the brine system can fall below
0 °C, this must be protected against freezing by adding
propylene glycol (NOTE: not ethanol). The mixing ratio should
be approximately 25% propylene glycol and the remainder
water. As a guideline for the volume calculation, use 1 litre
of ready-mixed brine per metre of collector hose (for 40 x
2.4 PN 6.3 PEM hose).

The installation has to be marked with the antifreeze used.
Fit a particle filter to the incoming pipe.

In the case of connection to an open groundwater system,
an intermediate frost-protected circuit must be provided,
because of the risk of dirt and freezing in the evaporator.
This requires an extra heat exchanger. In addition, the
ground water flow must be sufficiently large for all compon-
ents.

NOTE

This system solution means that the brine will also
circulate through the heating system.

Check that all component parts are designed for
the brine in question.

TIP

Ensure to post-tighten all hydraulic connections
again, both inside and outside HPAC S40, after
HPAC S40 is installed and mounted.

21

HPAC S40 | GB

Summary of Contents for HPAC S40

Page 1: ...HPAC S40 Installat rshandbok SE Klimatv xlingsmodul Installer manual GB Climate exchange module Installateurhandbuch DE Klimamodul UN IHB 2210 3 531577...

Page 2: ......

Page 3: ...ant information 19 General 21 Pipe connections 24 System diagram 25 Electrical connection 27 Program settings 30 Technical data Deutsch 31 Wichtige Informationen 32 Allgemeines 34 Rohranschluss 37 Sys...

Page 4: ...Kabelarea ska vara dimensionerad efter vilken avs kring som anv nds Om matningskabeln r skadad f r den en dast ers ttas av NIBE dess serviceombud eller liknande beh rig personal f r att und vika event...

Page 5: ...e tidigast efter 2 tim mar PASSIV KYLA Vid behov av passiv kyla startar cirkulationspumparna i v rmepumpen som cirkulerar v tska fr n mark bergkollek torn in i husets klimatsystem och kyler huset Kyla...

Page 6: ...orrt OBS Anv nd inte r ren som b rhandtag MONTERING HPAC S40 monteras p v ggen Skruva f rst upp den medlevererade upph ngningskonsolen p v ggen H ng sedan upp HPAC S40 p konsolen HPAC S40 r nu till vi...

Page 7: ...stigande mot v rme pumpen f r att undvika luftfickor Om det inte r m jligt ska h gpunkterna f rses med avluftningsm jligheter Kondensisolera systemets samtliga r r utom r ren till varmvattenberedaren...

Page 8: ...4 QN15 QN13 t nd t nd t nd t nd V rme sl ckt sl ckt t nd t nd Passiv kyla sl ckt sl ckt sl ckt sl ckt Aktiv kyla Ovanst ende g ller sp nningssatt anl ggning Pilen och figuren visar i vilket l ge venti...

Page 9: ...0 800 1000 10 20 30 40 50 Storlek l K ldb rarvolym l K ldb rarvolym l Storlek l KONDENSISOLERING F r att undvika kondensbildning m ste r rledningar och vriga kalla ytor isoleras med diffusionst tt mat...

Page 10: ...enligt g llande normer F RKLARING V rmepump EB100 Extern framledningsgivare BT25 Extern returledningsgivare BT71 HPAC S40 EQ1 Cirkulationspump kyla GP10 vrigt Utj mningsk rl UKV CP10 PRINCIPSCHEMA V...

Page 11: ...lossa l sa fast kablar i plin tar LEK 1 2 2 3 1 2 3 3 4 1 2 LEK 1 1 2 2 3 3 1 2 3 3 4 1 2 1 2 VERSIKT TILLBEH RSKORT AA5 ON 1 2 3 4 5 6 7 8 X9 X2 24 20 21 22 23 15 16 17 18 19 10 11 12 13 14 5 6 7 8 9...

Page 12: ...nds ska den externa framledningsgivaren BT25 anslutas till din kompatibla v rmepump Se installat rshandboken f r v r mepumpen OBS Givaren har styrande funktion f r kyla och v rme EXTERN RETURLEDNINGS...

Page 13: ...NY 1 1 TEMPERATUR H r g r du temperaturinst llningar f r anl ggningens klimat system MENY 1 1 2 KYLA Inst llningavtemperaturen medrumsgivare installerad och aktiverad Inst llningsomr de 5 35 C V rdet...

Page 14: ...as om din elleverant r st djer Smart price adaption om du har ett timprisbaserat elavtal och ett aktivt myUplink konto Smart price adaption anpassar del av v rmepumpens f r brukning ver dygnet till de...

Page 15: ...Tid mellan kyla och v rme H r st ller du in hur l nge anl gg ningen ska v nta innan den terg r till v rmedrift n r kylbe hovet har upph rt eller tv rt om Kyla v rmegivare H r v ljer du vilken givare s...

Page 16: ...0 100 120 80 100 TEKNISKA DATA HPAC S40 230V 50 Hz Sp nning 655 mm H jd 600 mm Bredd 415 mm Djup 5 17 kW Avsedd f r v rmepumpar R25 1 mm R ranslutning 40 kg Vikt Bly i m ssingsdetaljer mnen enligt f r...

Page 17: ...17 HPAC S40 SE...

Page 18: ...ambienttemper ature HPAC S40 must be installed via an isolator switch The cable area has to be dimen sioned based on the fuse rating used If the supply cable is damaged only NIBE its service represen...

Page 19: ...least 2 hours PASSIVE COOLING When passive cooling is required the circulation pumps in the heat pump start to circulate fluid from the surface soil rock collector through the building s distribution...

Page 20: ...a handle MOUNTING HPAC S40 is installed on the wall First screw the enclosed suspension bracket into place on the wall Then hang HPAC S40 on the bracket HPAC S40 can now be slid sideways to some exten...

Page 21: ...and on the climate system Ensure the collector hose rises constantly towards the heat pump to avoid air pockets If this is not possible airvents should be used All the system s pipes must be condensat...

Page 22: ...lit lit lit lit Heating not lit not lit lit lit Passive cooling not lit not lit not lit not lit Active cooling The above applies to powered systems The arrow and figure indicate in which position the...

Page 23: ...ween 1 0 and 1 5 bar 0 0 200 400 600 800 1000 10 20 30 40 50 Storlek l K ldb rarvolym l Brine volume l Size l CONDENSATION INSULATION Pipes and other cold surfaces must be insulated with diffu sion pr...

Page 24: ...ccording to applicable standards EXPLANATION Heat pump EB100 External supply temperature sensor BT25 External return line sensor BT71 HPAC S40 EQ1 Circulation pump cooling GP10 Miscellaneous Buffer ve...

Page 25: ...OCK Use a suitable tool to release lock cables in terminal blocks LEK 1 2 2 3 1 2 3 3 4 1 2 LEK 1 1 2 2 3 3 1 2 3 3 4 1 2 1 2 OVERVIEW ACCESSORY BOARD AA5 ON 1 2 3 4 5 6 7 8 X9 X2 24 20 21 22 23 15 16...

Page 26: ...perature sensor BT25 has to be con nected to your compatible heat pump See the Installer Manual for the heat pump NOTE The sensor has controlling functions for cooling and heating EXTERNAL RETURN LINE...

Page 27: ...RE Here you make temperature settings for your installation s climate system MENU 1 1 2 COOLING Set the temperature with room sensor installed and activated Setting range 5 35 C The value in the displ...

Page 28: ...s installed and activated the desired room temperature is decreased by 1 C instead MENU 4 2 5 SMART PRICE ADAPTION Affect cooling Alternative on off Degree of effect Setting range 1 10 This function c...

Page 29: ...me You can set the time over which the average outdoor temperature is calculated If you select 0 the cur rent outdoor temperature is used Time betw cooling and heating Here you set how long the instal...

Page 30: ...0 TECHNICAL SPECIFICATIONS HPAC S40 230V 50 Hz Voltage 655 mm Height 600 mm Width 415 mm Depth 5 17 kW Intended for heat pumps R25 1 mm Pipe connections 40 kg Weight Lead in brass components Substance...

Page 31: ...gen Schalter installiert werden Der Kabelquer schnitt muss der verwendeten Absicherung entsprechend dimensioniert sein Ein besch digtes Stromversorgungskabel darf nur von NIBE dem Servicebeauftrag ten...

Page 32: ...s 2 h vergehen PASSIVE K LTE Bei Bedarf an passiver K hlung starten die Umw lzpumpen in der W rmepumpe Sie bef rdern Fl ssigkeit vom Erd Felskollektor zum Klimatisierungssystem des Geb udes und k hlen...

Page 33: ...als Tragegriffe MONTAGE HPAC S40 wird an der Wand montiert Bringen Sie zun chst die mitgelieferte Aufh ngekonsole an der Wand an H ngen Sie dann HPAC S40 an der Konsole auf HPAC S40 l sst sich nun lei...

Page 34: ...hs zur W rmepumpe um die Bildung von Luftein schl ssen zu vermeiden Ist dies nicht m glich m ssen an den h chstgelegenen Punkten Entl ftungsm glichkeiten angebracht werden Alle Rohre im System mit Aus...

Page 35: ...ichneten Seite ge ffnet QN16 QN14 QN15 QN13 ein ein ein ein Heizung aus aus ein ein Passive K lte aus aus aus aus Aktive K hlung Die o g Vorgaben gelten f r eine mit Spannung versorgte Anlage Pfeil un...

Page 36: ...1000 10 20 30 40 50 Storlek l K ldb rarvolym l Volumen des W rmequellenmediums l Gr e l KONDENSISOLIERUNG Um eine Kondensatbildung zu vermeiden m ssen Rohrlei tungen und andere kalte Oberfl chen mit d...

Page 37: ...e Anlage muss gem den geltenden Normen geplant und montiert werden ERKL RUNG W rmepumpe EB100 Externer Vorlauff hler BT25 Externer R cklauff hler BT71 HPAC S40 EQ1 Umw lzpumpe K hlung GP10 Sonstiges A...

Page 38: ...rwenden Sie zum L sen bzw Befestigen von Kabeln an den Anschlussklemmen ein geeignetes Werkzeug LEK 1 2 2 3 1 2 3 3 4 1 2 LEK 1 1 2 2 3 3 1 2 3 3 4 1 2 1 2 BERSICHT ZUBEH RPLATINE AA5 ON 1 2 3 4 5 6 7...

Page 39: ...in Ausgleichsgef UKV zum Einsatz kommt ist der externe Vorlauff hler BT25 an Ihre kompatible W rmepumpe anzuschlie en Siehe Installateurhandbuch f r die W rmepumpe HINWEIS Der F hler steuert K hlung u...

Page 40: ...ntfernen es MEN 1 1 TEMPERATUR Hier nehmen Sie Temperatureinstellungen f r das Klimati sierungssystem der Anlage vor MEN 1 1 2 K HLUNG Temperatureinstellung mitinstalliertemund aktiviertem Raumf hler...

Page 41: ...ieb wird die Innenraumtemperatur nicht beeinflusst Im berkapazit tsmodus von SG Ready und im K hlbetrieb wird die Parallelverschiebung f r die Innentemperatur um 1 verringert Wenn ein Raumf hler insta...

Page 42: ...peraturen ein die die Anlage f r die Regelung im Automatikmodus verwenden soll ACHTUNG In Systemen in denen dieselben Rohre f r Heizung und K hlung genutzt werden kann Heizstopp maximal auf Start K hl...

Page 43: ...HINWEIS Die Zwangssteuerung wird nur bei einer St rungs suche genutzt Bei einer anderweitigen Nutzung der Funktion k nnen Komponenten in der Anlage besch digt werden 43 HPAC S40 DE...

Page 44: ...0 80 100 TECHNISCHE DATEN HPAC S40 230 V 50 Hz Spannung 655 mm H he 600 mm Breite 415 mm Tiefe 5 17 kW Vorgesehen f r W rmepumpen R25 1 mm Rohranschluss 40 kg Gewicht Blei in Messingbauteilen Stoffe g...

Page 45: ...JOV 2020 02 13 Production MJN 2012 08 16 0 001 WIR DIAGRAM HPAC 40 45 S40 S45 ELSCHEMA HPAC 40 45 S40 S45 450147 6 45 HPAC S40 Wiring diagram...

Page 46: ......

Page 47: ...1510 Vantaa Tel 358 0 9 274 6970 info nibe fi nibe fi NORWAY NETHERLANDS GREAT BRITAIN ABK Qviller AS Brobekkveien 80 0582 Oslo Tel 47 23 17 05 20 post abkqviller no nibe no NIBE Energietechniek B V E...

Page 48: ...n fr n NIBE Energy Systems Alla produktillustrationer fakta och data bygger p aktuell information vid tidpunkten f r publikationens godk nnande NIBE Energy Systems reserverar sig f r eventuella fakta...

Reviews: