Troubleshooting
NOTE
Work behind covers secured by screws may
only be carried out by, or under the supervision
of, a qualified installation engineer.
NOTE
As NIBE SPLIT HBS 05 can be connected to a
large number of external units, these should
also be checked.
NOTE
In the event of action to rectify malfunctions
that require work within screwed hatches the
incoming electricity must isolated at the safety
switch.
The following tips can be used to rectify comfort disrup-
tion:
Basic actions
First and foremost
Start by checking any alarm messages in the info menu
on the indoor module (VVM) / control module (SMO).
Follow the instructions on the display on the indoor
module (VVM) / control module (SMO).
NIBE SPLIT HBS 05 not in operation
NIBE SPLIT HBS 05 communicates all alarms to the indoor
module/control module (VVM / SMO).
■
Ensure that the HBS 05 and AMS 10 are connected to
the power source.
■
Check the indoor module or control module. See sec-
tion "Disturbances in comfort" in the Installer Manual
for the indoor module or control module (VVM / SMO).
NIBE SPLIT HBS 05 does not communicate
■
Check that the addressing of NIBE SPLIT HBS 05 is cor-
rect.
■
Check that the communication cable is correctly con-
nected and working.
Further possible measures
If any components are disconnected from the power.
Start by checking the following items:
■
That the heat pump is running or that the supply cable
to AMS 10 / HBS 05 is connected.
■
Group and main fuses of the accommodation.
■
The property's earth circuit breaker.
■
Check the indoor module or control module. See sec-
tion "Disturbances in comfort" in the Installer Manual
for the indoor module or control module (VVM / SMO).
■
Automatic personal protection (FB1) in
NIBE SPLIT HBS 05. (Only if KVR 10 is installed.)
Low hot water temperature or a lack of hot
water
NOTE
The hot water is always set on the indoor
module (VVM) or the control module (SMO).
This part of the fault-tracing chapter only applies if the
heat pump is docked to the hot water heater.
■
Large hot water consumption.
–
Wait until the hot water has heated up.
■
The hot water settings are adjusted on the display on
the indoor module / control module.
–
See the manual for the indoor module or control
module.
■
Clogged particle filter.
–
Check whether alarm "high condenser out" (162) is
an information message. Check and clean the
particle filter.
Low room temperature
■
Closed thermostats in several rooms.
–
Set the thermostats to max in as many rooms as
possible.
■
Incorrect settings in indoor module or control module.
–
See the manual for the indoor module / control
module (VVM / SMO).
■
Incorrect flow across the heat pump.
–
Check whether alarm "high condenser in" (163) or
"high condenser out" (162) are info messages. Follow
the instructions for adjusting charge flow.
High room temperature
■
Incorrect settings in indoor module or control module.
–
See the manual for the indoor module or control
module.
Large amount of water below the outdoor
module (AMS 10)
Check that the water drainage via the condensation pipe
(KVR 10) is working.
HBS 05
Chapter 8 |
Disturbances in comfort
32
8 Disturbances in comfort