Condensation drain:

When it is time to exchange the filter in the fall, check the 

condensation drain for fouling by dirt and make sure there 

is water in the waterseal. The waterseal must not dry out 

since the negative pressure of the aggregate will suck air 

into the aggregate causing the condensation to remain in 

the aggregate. Pour 1 litre of water into the condensation 

container and check that the flow is undeterred. If the 

condensation drain does not work correctly water damages 

may occur in the residence.

Counter-flow heat exchanger

The counter-flow heat exchanger must be overseen

every year. Remove it if it is dirty and vacuum it without

touching the plates. Open the front of the condensation

container before removing the counter-flow heat

exchanger. This is done by opening the spring latch on

the right corner of the condensation container. Push

lightly from behind when removing the counter-flow heat

exchanger.

Do not damage the plates. The effect will no 

longer be optimal if the plates are damaged.

Fans:

Remember to switch of the power supply!!

Check the fans in the fan wheel for dirt every third year.

The four outermost screws that hold the fans in place

must be removed in order to remove the fans. Remove

the front lid of the unit. Clean the fans using a brush, fan

brush or paintbrush.

 

The filter units must be removed  

 

before disassembling the front lid.

Incoming and outgoing units:

The ventilation unit must be cleaned regularly with a small

brush in order to maintain correct ventilation. Do not 

change the setting. N.B. Do not mix the units up when

many are cleaned at the same time.

12: Kondensvandsafløb

11: Kondensvandsbakke

9. Udsugningsfilter

7: Udsugningsventilator

6: Indblæsningsventilator

5: Modstrømsvarmeveksler

14: By-pass

13: 230V/50Hz

10: El-kasse

8: Friskluftfilter

4: Indblæsning

3: Udsugning

2: Afkast

1: Frisk luft

3

1

4

2

13

265

128.6

550

280

135

550

24

32

60.7

1014

42

1056

1088

The four outermost screws that hold the fans in

place must be removed in order to remove the

fans.

12: Kondensvandsafløb

11: Kondensvandsbakke

9. Udsugningsfilter

7: Udsugningsventilator

6: Indblæsningsventilator

5: Modstrømsvarmeveksler

14: By-pass

13: 230V/50Hz

10: El-kasse

8: Friskluftfilter

4: Indblæsning

3: Udsugning

2: Afkast

1: Frisk luft

3

1

4

2

13

265

128.6

550

280

135

550

24

32

60.7

1014

42

1056

1088

Condensation drain

Counter-flow  

heat exchanger

Spring latch,  

condensation container

Summary of Contents for GV-HR110

Page 1: ...k NIBE A S Sverigesvej 6 DK 6100 Haderslev Tlf 45 7353 2700 www NIBE dk NIBE AB Sweden Box 14 Hannabadsv gen 5 SE 285 21 Markaryd www NIBE eu INSTALLATIONS MANUAL Passive ventilation Heat recovery GV...

Page 2: ...tics 7 Insulating ducts in warm rooms 8 Reheating of the supply air 8 Electric installations 9 Control and settings of the facility 9 Optimal adjustment of the facility 9 Facility maintenance 10 Troub...

Page 3: ...a thermostat and an electric heating element that switches on when the temperature falls below 2 C IMPORTANT IMPORTANT IMPORTANT IMPORTANT 7 Set the amount of incoming 1 and outgoing air before using...

Page 4: ...r 10 El kasse 11 Kondensvandsbakke 12 Kondensvandsafl b 13 230V 50Hz 14 By pass 2 4 13 72 7 60 7 550 42 1014 24 32 1088 1056 550 135 280 4 Subject to Technical Modifications of GV HR110 GV HR110 Assem...

Page 5: ...in the picture A A Visible wall mountings Concealed wall mountings Cabinet assembly gummif dder som leveret ved vandret montage af maskinen skal de leverede gummif dder flyttes til positioner som anvi...

Page 6: ...he condensation drain side The waterseal must be airtight e g by bending a 15 mm copper pipe as a waterseal see the drawing on the left A reinforced water hose is attached between the drain connection...

Page 7: ...even thicker insulation to avoid warm air in the attic from heating the incoming air during the summer Make sure that the closures are tight where the exhaust air duct comes through the roof or throu...

Page 8: ...ated in menu 4 5 User menu and that the setpoint temperature is set in menu 4 8 Service Menu Recommended setpoint is 3 C Reheating of the supply air Since the counterflow heat exchanger cannot recycle...

Page 9: ...ectly mounted with a waterseal and that it is protected from frost Pour 1 litre of water into the condensation container and check that it flows unimpeded through the condensation drain pipe 5 Set all...

Page 10: ...the procedure both knobs must be turned one quarter turn clockwise to the right When the filter has been exchanged or cleaned by shaking them to remove most of the dirt the filter timer is set by pre...

Page 11: ...amage the plates The effect will no longer be optimal if the plates are damaged Fans Remember to switch of the power supply Check the fans in the fan wheel for dirt every third year The four outermost...

Page 12: ...st No incoming air to the residence Error Faulty fan Fouled incoming air filter Fouled outside air grid A fuse has blown on the circuit board No power supply to the facility No exhaust air from the re...

Page 13: ...Belimo Bypass 230VAC H7 R10 Fan extract air 230VAC H8 R12 ON OFF Bypass 2x230VAC H9 R10 Fan supply air 230VAC bypass H16 R8 AUX relay 230VAC max 20W H17 R9 AUX relay 230VAC max 20W 1 1 1 1 1 1 1 1 1 1...

Page 14: ...Brown Brown Blue Blue Yellow green Yellow green Water valve Belimo Bypass Humidity sensor White Red Blue EC fan Supply air Aux relay R8 1x230V 50Hz ONLY control current Red Brown Blue Green Yellow Wh...

Page 15: ...dards hergestellt Directive a Machinery 2006 42 EC 15 March 2006 b Low Voltage 2006 95 EU 12 December 2006 c Electromagnetic Compatibility 2004 108 EC 15 December 2004 d Radio Telecommunication 99 5 E...

Page 16: ...294 71 Benatky nad Jizerou Tel 420 326 373 801 Fax 420 326 373 803 E mail nibe nibe cz www nibe cz PL NL FI DK DE CZ NIBE Energy Systems OY Juurakkotie 3 01510 Vantaa 3C Broom Business Park Bridge Wa...

Reviews: