background image

Installer manual

LEK

LEK

LEK

NIBE™ F2040

8, 12, 16 kW

Air/water heat pump

IHB GB 1512-3

231844

Summary of Contents for F2040 Series

Page 1: ...Installer manual LEK LEK LEK NIBE F2040 8 12 16 kW Air water heat pump IHB GB 1512 3 231844...

Page 2: ......

Page 3: ...ocking alternatives 22 5 Electrical connections 22 General 24 Connections 30 6 Commissioning and adjusting 30 Preparations 30 Filling and venting the heating medium sys tem 30 Compressor heater 31 Sta...

Page 4: ...any design or technical modifications are reserved NIBE 2015 Symbols NOTE This symbol indicates danger to machine or person Caution This symbol indicates important information about what you should ob...

Page 5: ...l number Caution Always give the product s serial number when reporting a fault Country specific information Installer manual This installer manual must be left with the customer 3 Chapter 1 Important...

Page 6: ...qualified person Fill in the page for information about installation data in the User manual Date Signature Notes Description System flushed System vented Particle filter Shut off and drain valve Char...

Page 7: ...u Pou du Ciel 01600 Reyrieux FR Tel 04 74 00 92 92 Fax 04 74 00 42 00 E mail info nibe fr www nibe fr NIBE Energy Systems Ltd 3C Broom Business Park Bridge Way Chesterfield S41 9QG GB Tel 0845 095 120...

Page 8: ...ulation of the outdoor air can occur This causes lower output and impaired efficiency The evaporator should be sheltered from direct wind which negatively affects the defrosting function Place F2040 p...

Page 9: ...y the heating cable to prevent freezing Route the pipe downward from F2040 The outlet of the condensation water pipe must be at a depth that is frost free or alternatively indoors with reservation for...

Page 10: ...ation area The distance between F2040 and the house wall must be at least 150 mm Clearance in front of F2040 should be at least one metre 50 255 St llbar 40 50 955 243 512 110 395 265 50 452 1075 1145...

Page 11: ...Removing the covers F2040 8 LEK F2040 12 LEK F2040 16 LEK Removing the front panel F2040 8 LEK 9 Chapter 2 Delivery and handling NIBE F2040...

Page 12: ...F2040 12 LEK F2040 16 LEK Removing the side panel F2040 12 LEK F2040 16 LEK DATA NIBE F2040 Chapter 2 Delivery and handling 10...

Page 13: ...PWB2 PWB3 PWB1 BT12 BT15 BP4 QN2 BT3 PF3 HS1 EP2 GQ10 QN1 BP2 QM35 QM36 BP1 QN3 CH EB10 AA23 X1 F TB BT14 Tho D Tho S BT17 LEK DATA XL2 UB1 UB2 W1 XL1 UB3 LEK DATA PF1 PF3 Tho A BT28 Tho R1 Tho R2 BT1...

Page 14: ...B1 PWB2 PWB3 DH UB3 BT3 BP4 PF3 BT15 EP1 EP2 HS1 BP2 BT12 X1 EB11 CM 20S 63H1 LPT SM2 SM1 FM01 CH EB10 AA23 Tho D BT14 BT17 Tho S LEK DATA XL2 UB1 UB2 W1 XL1 UB3 LEK DATA Tho A BT28 PF1 PF3 Tho R1 BT1...

Page 15: ...X1 CM 63H1 CH SM2 SM1 FM01 PWB2 PWB3 PWB1 QN2 20S BT12 TB BP1 PF3 QN3 BP4 BT3 BT15 UB3 GQ10 HS1 QN1 EP2 QM36 QM35 EB11 GQ2 FM02 EP1 F LPT BP2 AA23 Tho D BT14 EB10 Tho S BT17 13 Chapter 3 The heat pum...

Page 16: ...LEK DATA XL2 UB1 UB2 XL1 UB3 W1 LEK DATA PF3 PF1 BT28 Tho A Tho R1 Tho R2 BT16 NIBE F2040 Chapter 3 The heat pump design 14...

Page 17: ...oor unit AA23 S3 Terminal block KVR AA23 X1 Terminal block communication from indoor module AA23 X4 Communication with TB AA23 X100 Compressor heater EB10 CH Drip tray heater EB11 DH Main fuse compres...

Page 18: ...heater EB10 CH Drip tray heater EB11 DH Main fuse compressor unit F Fan GQ1 FM01 Fan GQ2 FM02 Control board PWB1 Inverter board PWB2 Filter board PWB3 Terminal block incoming supply and com municatio...

Page 19: ...el Bakre el LEK LE EB11 PWB3 PWB1 EB10 AA23 FM01 TB F AA23 F3 AA23 X4 AA23 X1 DH CH GQ1 AA23 S3 AA23 X100 Bakre el LEK LEK PWB2 Capacitor Reactor AF module Diode module 17 Chapter 3 The heat pump des...

Page 20: ...akre el LEK PWB3 PWB1 EB10 FM01 AA23 X4 DH CH GQ1 TB AA23 X1 AA23 F3 EB11 F AA23 AA23 S3 FM02 GQ2 AA23 X100 Bakre el LEK LEK PWB2 PWB2 Capacitor Reactor AF module Diode module NIBE F2040 Chapter 3 The...

Page 21: ...contaminants do not damage the components Pipe coupling heating medium circuit F2040 can be connected directly to the heating sys tem see the section Docking or according to one of the system solution...

Page 22: ...F2040 8 LEK Heat insulation F2040 12 LEK DATA LEK Heat insulation F2040 16 LEK DATA NIBE F2040 Chapter 4 Pipe connections 20...

Page 23: ...d ance with current regulations for all docked options See www nibe eu for more docking options Connecting accessories Instructions for connecting accessories are in the install ation instructions pro...

Page 24: ...on boards with fuses If an insulation test is to be carried out in the building disconnect the heat pump Communication cable W2 is inserted from the rear side through UB2 Connect communication cable W...

Page 25: ...CH AA23 FM01 TB F AA23 F3 AA23 X1 PWB1 AA23 X4 AA23 S3 Bakre el LEK LEK PWB2 F2040 16 Fr mre el Bakre el LEK LEK DH PWB3 CH AA23 FM01 TB F AA23 F3 AA23 X1 PWB1 AA23 X4 AA23 S3 Bakre el LEK LEK PWB2 23...

Page 26: ...and or sensor to external connections cables must not be laid closer than 20 cm to high voltage cables when cable routing Power connection F2040 8 LEK DATA LEK Incoming supply Power connection W1 XL2...

Page 27: ...F2040 12 LEK DATA LEK Incoming supply W1 W1 UB2 UB1 XL1 XL2 UB3 Power connection 25 Chapter 5 Electrical connections NIBE F2040...

Page 28: ...able W2 provided by in staller to terminal block AA23 X4 and secure with two cable ties see image For connection of accessory KVR 10 heating cable EB14 is connected via cable grommet UB3 see Extern al...

Page 29: ...eads EMI filters LEK F2040 12 LEK Secure the communication cable W2 here using two cable ties Fr mre el Bakre el LEK LEK F2040 16 LEK Fr mre el Bakre el LEK LEK Secure the communication cable W2 here...

Page 30: ...lock X1 4 6 according to following image 5 6 4 2 3 1 External F2040 X1 EB14 External heat cable AA23 F3 NOTE The pipe must be able to withstand the heat from the heating cable To ensure this function...

Page 31: ...the following image Innemodul X4 F2040 GND GND B B A 15 14 13 A GND B A AA3 1 2 3 4 5 6 External F2040 X4 AA3 For connection of indoor module see relevant manual on www nibe eu Addressing via cascade...

Page 32: ...venting nipple QM20 on the enclosed flexible hose and possibly the cir culation pump LEK QM20 Compressor heater F2040 is equipped with a compressor heater that heats the compressor before start up an...

Page 33: ...r 6 8 hours the communication cable W2 is connected to terminal block AA23 X4 7 Restart the indoor module Follow the instructions for Start up and inspection in the installation manual for the indoor...

Page 34: ...er and venting may be necessary If bubbling sounds can be heard from the heat pump the circulation pump and radiat ors the entire system will require further venting When the system is stable correct...

Page 35: ...adjusting hot water charging are in the installation manual for the respective indoor section See page 42 for the list of the indoor sections and ac cessories that can be used with F2040 33 Chapter 6...

Page 36: ...ction is to be activ ated for the heat pump here During active function you can limit the value of the maximum current Setting range 6 32 A Factory setting 32 A Stop temperature compressor Here you ca...

Page 37: ...tracing chapter only applies if the heat pump is docked to the hot water heater Large hot water consumption Wait until the hot water has heated up Incorrect settings in the indoor module See the manu...

Page 38: ...r BP4 Temperature sensor heating medium return line BT3 Temperature sensor condenser supply line BT12 Temperature sensor hot gas BT14 Tho D Temperature sensor fluid pipe BT15 Temperature sensor heat e...

Page 39: ...nection to card AA23 BP4 BT15 BT12 BT3 AA23 S3 Sensor placement in F2040 Defrost Cooling Defrost Cooling kW kW kW Defrost Cooling Defrost Cooling kW kW kW 37 Chapter 8 Disturbances in comfort NIBE F20...

Page 40: ...Resistance kOhm Temperature C 3 256 351 0 40 3 240 251 6 35 3 218 182 5 30 3 189 133 8 25 3 150 99 22 20 3 105 74 32 15 3 047 56 20 10 2 976 42 89 5 2 889 33 02 0 2 789 25 61 5 2 673 20 02 10 2 541 1...

Page 41: ...the heat pump runs the de frosting procedure Not an alarm but an operating status Defrosting in progress 183 Insufficient air circulation or blocked heat exchanger Open circuit or short circuit on inp...

Page 42: ...Hightemperatureinheat exchanger 261 Can occur when 15V power supply to the inverter PCB is unstable When IPM Intelligent power module displays FO signal Fault Output five times during a 60 minute peri...

Page 43: ...does not work see section Disturbances in comfort Defective control board in F2040 Sensor fault hot gas in F2040 Tho D Sensor fault Tho D 279 Open circuit or short circuit on sensor input Sensor does...

Page 44: ...ol module Part no 067 225 Wall mounting Wall mounting F2040 8 Part no 067 210 Wall mounting F2040 12 Part no 067 210 Water heater Accumulator tank VPA 300 200 Water heater with double jacketed vessel...

Page 45: ...95 15 90 40 F2040 Adjustable 40 50 Accessory KVR 10 is required F2040 12 50 255 St llbar 40 50 955 243 512 110 395 265 50 452 1075 1145 108 40 14 85 150 mm Fritt utrymme bakom 600 mm 400 mm 600mm Adj...

Page 46: ...55 243 512 110 395 265 50 452 14 85 150 mm Fritt utrymme bakom Min avst nd vid anv ndning av flera F2040 600 mm 3000 mm 400 mm 600mm Minimalt fritt utrymme Minimalt fritt utrymme Fritt utrymme framf r...

Page 47: ...rences in ground level etc and should therefore only be seen as guide values F2040 adjusts the fan speed depending on the ambient temperature and evaporation temperature 2 m 6 m 10 m 2 m LEK F2040 16...

Page 48: ...52 11 20 3 20 3 50 27 18 C Specified supplied power EER 13 04 4 53 2 88 9 45 3 41 2 77 7 10 2 65 2 68 35 7 C 15 70 5 04 3 12 11 20 3 58 3 12 9 19 2 98 3 08 35 18 C Electrical data 230V 50 Hz 230V 2AC...

Page 49: ...heating medium ext thread Dimensions and weight 1145 1145 1035 mm Width 452 452 422 mm Depth 1450 50 0 995 50 0 895 50 0 mm Height with stand 135 105 90 kg Weight excl packaging Miscellaneous IP 24 E...

Page 50: ...ly temperature Return temp During shorter time it is allowed to have lower working temperatures on the water side e g during start up Working range compressor operation cooling F2040 8 12 16 65 58 55...

Page 51: ...12 00 kW T out Max avgiven effekt F2040 8 35 45 55 0 00 1 00 2 00 3 00 4 00 5 00 COP COP F2040 8 35 45 55 15 10 5 5 10 15 20 25 0 T out 15 10 5 5 10 15 20 25 0 COP F2040 8 Max specified output F2040 8...

Page 52: ...ffekt F2040 12 35 45 55 0 00 1 00 2 00 3 00 4 00 5 00 6 00 COP COP F2040 12 35 45 55 T out 15 10 5 5 10 15 20 25 0 T out 15 10 5 5 10 15 20 25 0 Outdoor temperature Outdoor temperature Max specified o...

Page 53: ...040 16 35 45 55 0 00 1 00 2 00 3 00 4 00 5 00 6 00 COP COP F2040 16 35 45 55 T out 15 10 5 5 10 15 20 25 0 T out 15 10 5 5 10 15 20 25 0 Outdoor temperature Outdoor temperature Max specified output F2...

Page 54: ...00 kW 35 45 55 35 45 55 35 45 55 T ute 15 10 5 5 10 15 20 25 0 T ute 15 10 5 5 10 15 20 25 0 T ute 15 10 5 5 10 15 20 25 0 kW 0 00 8 00 6 00 4 00 2 00 10 00 12 00 14 00 16 00 0 00 5 00 10 00 15 00 20...

Page 55: ...Electrical circuit diagram F2040 8 53 Chapter 11 Technical data NIBE F2040...

Page 56: ...OR GR 1 F P BK BK 4A 2 3 Tho P BP1 63H1 BT14 Tho D BT16 Tho R1 BT17 Tho S BT28 Tho A BP2 LPT 20S QN2 EB10 CH EB11 DH 2 1 1 2 3 4 5 6 AA23 X1 AA23 X100 Matning 230V 50 Hz NIBE F2040 Chapter 11 Technica...

Page 57: ...F2040 12 55 Chapter 11 Technical data NIBE F2040...

Page 58: ...1 WH RD BK CNIP Y Tho P BK BK OR CNFAN1 WH BL 7 BR 6 WH 5 4 RD 1 CNH BR BP1 63H1 Two fan unit only Two fan unit only BK BK CNS RD CNR WH CNF BK BL BL EB10 CH BR BR BT14 Tho D BK BK BT16 Tho R1 BK BK C...

Page 59: ...F2040 16 57 Chapter 11 Technical data NIBE F2040...

Page 60: ...RD 6 BL 4 OR 3 Y 2 WH 1 WH RD BK CNIP Y Tho P BK BK OR CNFAN1 WH BL 7 BR 6 WH 5 4 RD 1 CNH BR BP1 63H1 Two fan unit only BK BK CNS RD CNR WH CNF BK BL BL EB10 CH BR BR BT14 Tho D BK BK BT16 Tho R1 BK...

Page 61: ...on to rear side standard or underneath al ternative 24 External heating cable KVR 10 28 F Filling and venting the heating medium system 30 I Important information 2 Safety information 2 Inspection of...

Page 62: ......

Page 63: ......

Page 64: ...231844 NIBE AB Sweden Hannabadsv gen 5 Box 14 SE 285 21 Markaryd info nibe se www nibe eu...