Technical specifications
IP 21
F2040-16
F2040-12
F2040-8
F2040-6
Air/water heat pump
Output data
Nominal
Nominal
Nominal
Nominal
Outdoor temp./
Supply temp.
Heating
7.03/1.45/4.85
5.21/1.09/4.78
3.86/0.83/4.65
2.67/0.5/5.32
7/35 °C (floor)
Output data according to EN14511
Δ
T5K
9.33/2.38/3.92
6.91/1.79/3.86
5.11/1.36/3.76
2.32/0.55/4.2
2/35 °C (floor)
Capacity / supplied capacity / COP (kW/kW/-)
6.75/1.74/3.88
5.00/1.31/3.82
3.70/1.00/3.70
2.28/0.63/3.62
7/45 °C
9.18/2.98/3.08
6.80/2.24/3.04
5.03/1.70/2.96
1.93/0.67/2.88
2/45 °C
Max
Outd. temp: /
Supply temp.
Cooling
13.30/3.99/3.33
9.87/3.16/3.13
7.52/2.37/3.17
5.87/1.65/3.56
27/7 °C
Output data according to EN14511
Δ
T5K
17.70/4.52/3.91
11.70/3.32/3.52
11.20/3.20/3.50
7.98/1.77/4.52
27/18 °C
Capacity / supplied capacity / EER
13.04/4.53/2.88
9.45/3.41/2.77
7.10/2.65/2.68
4.86/1.86/2.61
35/7 °C
15.70/5.04/3.12
11.20/3.58/3.12
9.19/2.98/3.08
7.03/2.03/3.45
35/18 °C
Electrical data
230V ~50Hz, 230V 2AC ~50Hz
Rated voltage
25
23
16
15
A
rms
Max operating current, heat pump
24
22
15
14
A
rms
Max operating current, compressor
5
A
rms
Starting current
2 x 86
86
86
50
W
Nominal output, fan
25
25
16
16
A
rms
Fuse
1)
Refrigerant circuit
R410A
Type of refrigerant
2,088
GWP refrigerant
Twin Rotary
Type of compressor
M-MA68
Compressor oil
4.0
2.9
2.55
1.5
kg
Volume
8.35
6.06
5.32
3.13
t
CO
2
equivalent
4.15 (41.5 bar)
-
MPa
Cut-out value pressostat HP
-
4.15 (41.5
bar)
Cut-out value HP
0.079 (0.79 bar)
-
MPa
Cut-out value pressostat LP
Brine
6,000
4,380
3,000
2,530
m
3
/h
Airflow
-20 / 43
°C
Min. / Max. air temp.
Reverse cycle
Defrosting system
Heating medium
0.05/0.25 (0.5/4.5bar)
MPa
Min/Max system pressure heating medium
150
80
50
20
l
Min volume, climate system, heating/cooling
150
100
80
50
l
Min volume, climate system, under floor
cooling
0.79
0.57
0.38
0.29
l/s
Max flow, climate system
59
Chapter 11 |
Technical data
F2040
Summary of Contents for F2040-12
Page 1: ...Installer manual LEK LEK LEK UN F2040 6 8 12 16 Air water heat pump IHB EN 1746 6 231844 ...
Page 2: ......
Page 47: ...Connection to board AA23 BP4 BT15 BT12 BT3 AA23 S3 47 Chapter 8 Disturbances in comfort F2040 ...
Page 74: ...F2040 Chapter 11 Technical data 74 ...
Page 77: ...F2040 12 77 Chapter 11 Technical data F2040 ...