GB
13
The minimum distance in front of
the stove opening to combustible
parts of the building or interior
decoration must be at least 1,1 m.
E = minimum height to sloped ceiling
from the centre of the chimney
Installation distances
Permitted area for
combustible parts
of the building
* There must be a minimum distance of 50 mm/285 mm. If mounting on Contura’s corner bracket, the distance must be 56 mm/291 mm.
** To prevent discolouration of painted non-flammable walls we recommend that the same side distance as to combustible walls is used.
INSTALLATION AGAINST COMBUSTIBLE WALLS
INSTALLATION AGAINST FIREWALLS
C856W Style
465
Mi
n 300
697
Mi
n 1000
Combustible roof
106
563
59
380
Ø150
Air inlet Ø67
730
500
300
100
400
100
200
196
11
380
Combustible wall
Fire-retardant wall of
brick or concrete
430**
800
1100
196
380
11
200**
Fire-retardant wall of
brick or concrete
E 630
Mi
n 300
697
Mi
n 1000
750
750
50*
50*
285*
285*
Fire-retardant wall of
brick or concrete