Performance Data – TFC036
Heat Rejection
Capacity
Air Temp Entering
Fluid Cooler (DB)
Air ΔT
Water Flow Rate
Water Temp
Entering Fluid
Cooler
Water ΔT
through Fluid
Cooler
Approach
Temp
Fan Power
BTUH
°F
°F
GPM
°F
°F
°F
Watts
20412
70
12
9
85
5
11
44
27450
70
16
90
6
14
44
34433
70
20
95
8
17
44
21680
90
12
105
5
10
44
28634
90
16
110
6
14
45
35212
90
20
115
8
17
45
20097
105
12
120
4
11
45
27891
105
16
125
6
14
47
35067
105
20
130
8
17
47
Interpolation is permissable, extrapolation is not.
All performance data is based upon the lower voltage of dual voltage rated units.
Heat Rejection
Capacity
Air Temp Entering
Fluid Cooler (DB)
Air ΔT
Water Flow Rate
Water Temp
Entering Fluid
Cooler
Water ΔT
through Fluid
Cooler
Approach
Temp
Fan Power
BTUH
°F
°F
GPM
°F
°F
°F
Watts
28900
70
10
9
85
6
9
121
38700
70
14
90
9
12
121
48600
70
17
95
11
14
121
29600
90
10
105
7
9
126
39800
90
14
110
9
11
126
49800
90
18
115
11
14
126
29300
105
11
120
6
9
133
39400
105
14
125
9
11
134
49500
105
18
130
11
14
133
Interpolation is permissable, extrapolation is not.
All performance data is based upon the lower voltage of dual voltage rated units.
Low Speed
High Speed
3T @ 9 GPM (3 GPM/Ton)
EAT
EWT
GPM
Water ΔP*
70
85
9
1.8
70
90
9
1.8
70
95
9
1.8
90
105
9
1.8
90
110
9
1.8
90
115
9
1.8
105
120
9
1.9
105
125
9
1.9
105
130
9
1.9
* Pressure drop in PSI
Pressure Drop