Network Controller 6 Mounting and Wiring Guide
Updated: January 16, 2012
Preparation
Included in this Package
2
Preparation
Unpack the T-600 and power module (NPB-PWR, NPB-PWR-UN, or WPM-
XXX
) and inspect the package
contents for damaged or missing components. If damaged, notify the appropriate carrier at once and return any
damaged components for immediate repair or replacement. See
•
•
Included in this Package
Included in this package you should find the following items:
•
a T-600 or T-600-USA base controller.
•
This
T-600 (JACE 6) Mounting and Wiring Guide
, Part Number 11843 Rev 2.1
•
a hardware bag containing the following items:
–
A grounding wire, with quick-disconnect 0.187” female connector.
•
a power module (if ordered), which is required for operation.
The power module can be one of the following:
–
: 24Vac in-line, DIN-mount capable, with grounding wire,
or
–
: 90-263 Vac in-line, DIN-mount capable, with grounding wire,
or
–
: External wall-mount power adapter (input: 90–254Vac, 50–60 Hz, output: 15Vdc, 1A)
where
XXX
varies by the AC wall plug (for installation locale), such as:
WPM-US
(U.S. or Japan installations), WPM-EUR (European installations, type “C” plug)
WPM-UK (United Kingdom installations, type “B” plug)
Material and Tools Required
The following supplies and tools may be required for installation:
•
DIN rail, type NS35/7.5 (35mm x 7.5mm) and DIN rail end-clips (stop clips), recommended for any
installation that includes NPB-PWR or NPB-PWR-UN module and/or optional I/O modules.
Note
Length of DIN rail is determined by the number of optional DIN-mounted options.
on page 6 for more details.
•
If using a NPB-PWR power module, either one of the following:
–
UL listed, Class 2, 24Vac transformer, rated at minimum of 8.5VA to 20VA (approximate range of
JACE-2 alone, to fully-expanded unit with four additional T-IO-16 modules and other option boards).
Note that a
dedicated
transformer is required (cannot also power additional equipment).
–
24Vdc power supply, capable of supplying at least 1A (24W).
•
Suitable screws and screwdriver for mounting DIN rail, or if DIN rail not used, for mounting bases of
T-600 controller, NPB-PWR or NPB-PWR-UN module (if used), and any I/O modules (if used).
•
#2 phillips screwdriver: used to install and remove optional communications modules.
•
Small flat-blade screwdriver: used for mounting or removing the T-600 from DIN rail, also for making
wiring connections to RS-485 connector, and optionally LON and I/O connectors.