5

SCC-RLY01 Relay Module User Guide

Caution

The SCC-RLY01 module is derated to 30 V maximum switching voltage in the 

SC-2345 carrier regardless of any other voltage markings found on the SCC-RLY01 
module case.

Signal bandwidth.................................... DC to 400 Hz

Contact resistance .................................. 30 m

 max

Switching time

Operate time (NC to NO)................ 5 ms (10 ms max)

Release time (NO to NC)................ 4 ms (5 ms max)

1

Maximum operating speed..................... 30 cps at rated load

Contact lifetime...................................... 5 

×

 10

7

 operations at 180 cpm 

(minimum)

Power Requirement

Digital power.......................................... 300 mW max

+5 V........................................................ 60 mA max

Physical

Figure 3.  

SCC

-

RLY01 Dimensions

Weight .................................................... 37 g (1.3 oz)

1   

Excluding contact bounce time

1.87 cm

(0.74 in.)

7.93 cm

(3.12 in.)

3.55 cm

(1.4 in.)

Summary of Contents for SCC-RLY01

Page 1: ...nt a range of values associated with a bit or signal name for example P0 3 0 The symbol leads you through nested menu items and dialog box options to a final action The sequence File Page Setup Option...

Page 2: ...ries programs subprograms subroutines device names functions operations variables filenames and extensions SC 2345 SC 2345 refers to both the SC 2345 connector block and SC 2345 with configurable conn...

Page 3: ...manuals Installing the Module Caution Refer to the Read Me First Safety and Radio Frequency Interference document before removing equipment covers or connecting disconnecting any signal wires Plug the...

Page 4: ...kshell Figure 2 High Voltage Backshell For information about how to configure the SCC RLY01 module with NI DAQmx refer to the SCC Quick Start Guide Specifications These ratings are typical at 25 C unl...

Page 5: ...e Signal bandwidth DC to 400 Hz Contact resistance 30 m max Switching time Operate time NC to NO 5 ms 10 ms max Release time NO to NC 4 ms 5 ms max 1 Maximum operating speed 30 cps at rated load Conta...

Page 6: ...ion to signals in Measurement Category II III or IV Do not connect to MAINS When used with an SCC 68 Channel to earth inputs 300 VDC Measurement Category II1 Caution Do not use for connection to signa...

Page 7: ...ts Minimum Immunity EN 55011 Emissions Group 1 Class A CE C Tick ICES and FCC Part 15 Emissions Class A Note For EMC compliance operate this device according to product documentation CE Compliance Thi...

Page 8: ...on the bottom of the module Figure 4 SCC Module Bottom View Table 1 lists the signal connection corresponding to each pin GND is the reference for the 5 V supply 1 Pin 1 2 Pin 2 3 PWB Key 4 Pin 19 5 P...

Page 9: ...any names mentioned herein are trademarks or trade names of their respective companies For patents covering National Instruments products refer to the appropriate location Help Patents in your softwar...

Reviews: