NI cRIO-9081
12
7
8
11
1
2
9
10
4
6
5
3
13
1. LEDs
2. Power Connector
3. RJ-50 RS-485 Serial Port
4. Grounding Screw
5. USB Ports 1-4
6. USB Retention Standoff
7. RJ-45 Ethernet Ports 1 and 2
8. MXI Express Connector
9. VGA Video Connector
10. RS-232 Serial Port
11. Power Button
12. Reset Button
13. DIP Switches
Connecting the cRIO-9082 to Ground
You must connect the cRIO-9082 grounding terminal to the grounding electrode system of the
facility.
What to Use
•
Ring lug
•
Wire, 1.6 mm
2
(14 AWG) or larger
•
Screwdriver, Phillips #2
What to Do
Complete the following steps to ground the cRIO-9082.
1.
Attach the ring lug to the wire.
2.
Remove the grounding screw from the grounding terminal on the cRIO-9082.
3.
Attach the ring lug to the grounding terminal.
4.
Tighten the grounding screw to 0.5 N · m (4.4 lb · in.) of torque.
5.
Attach the other end of the wire to the grounding electrode system of your facility using a
method that is appropriate for your application.
6
|
ni.com
|
NI cRIO-9082 Getting Started Guide