Installation
19
TemBreak
PRO
B_BE-UM-001-EN
– V1.1.0
Clearances
Phase to Phase and Earth
Interruption of large currents during fault or normal switching operation produces ionised gases and arcing materials which expelled from the vents at the top
of the MCCB. These ionised gases are highly conductive, concentrated, and at an elevated temperature when it exits the MCCB via the arc vents. Care
must be taken to avoid an arcing fault from occurring due to the presence of concentrated ionised gases creating a conductive path between exposed
conductors. Incoming conductors must therefore be insulated the full length up to the terminal opening of the MCCB, ensuring bare conductors are not
exposed directly to concentrated ionised gases. This also applies to the attached busbars supplied as part of the MCCB.
Interpole barriers or terminal covers may be used to achieve creepage and clearance requirements. Conductors must not impede the flow of ionised gas
and allow it to clear and disperse safety. Interpole barriers are supplied as standard with Terasaki MCCBs for the line side only. 2 barriers with 3P MCCBs
and 3 with 4P MCCBs. In cases where two different MCCB types are installed one above the other, the insulation distance between the two models should
be as for the lower model.
WARNING
: Exposed conductors including terminals at attached busbars must be insulated to avoid possible
short-circuit or earth faults due any foreign matter coming into contact with the conductors.
Summary of Contents for TemBreak PRO
Page 45: ...45 TemBreak PRO B_BE UM 001 EN V1 1 0 Annex A Dimensions B250P ...
Page 46: ...Annex A Dimensions B250 46 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 47: ...Annex A Dimensions 47 TemBreak PRO B_BE UM 001 EN V1 1 0 B400P R ...
Page 48: ...Annex A Dimensions B400P R 48 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 49: ...Annex A Dimensions 49 TemBreak PRO B_BE UM 001 EN V1 1 0 B800N H G ...
Page 50: ...Annex A Dimensions B800N H G 50 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 51: ...Annex A Dimensions 51 TemBreak PRO B_BE UM 001 EN V1 1 0 B800P R ...
Page 52: ...Annex A Dimensions B800P R 52 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 53: ...Annex A Dimensions 53 TemBreak PRO B_BE UM 001 EN V1 1 0 B1000N H ...
Page 54: ...Annex A Dimensions B1000N H 54 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 55: ...Annex A Dimensions 55 TemBreak PRO B_BE UM 001 EN V1 1 0 B1250N H HL ...
Page 56: ...Annex A Dimensions B1250N H HL 56 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 57: ...Annex A Dimensions 57 TemBreak PRO B_BE UM 001 EN V1 1 0 B1600N HL ...
Page 58: ...Annex A Dimensions B1600N HL 58 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 89: ...89 TemBreak PRO B_BE UM 001 EN V1 1 0 Annex C I2t Let Through Curves B250P ...
Page 90: ...Annex C I2t Let Through Curves 90 TemBreak PRO B_BE UM 001 EN V1 1 0 B400P R ...
Page 91: ...Annex C I2t Let Through Curves 91 TemBreak PRO B_BE UM 001 EN V1 1 0 B800N H G ...
Page 92: ...Annex C I2t Let Through Curves 92 TemBreak PRO B_BE UM 001 EN V1 1 0 B800P R ...
Page 93: ...Annex C I2t Let Through Curves 93 TemBreak PRO B_BE UM 001 EN V1 1 0 B1000N H ...
Page 94: ...Annex C I2t Let Through Curves 94 TemBreak PRO B_BE UM 001 EN V1 1 0 B1250N H HL ...
Page 95: ...Annex C I2t Let Through Curves 95 TemBreak PRO B_BE UM 001 EN V1 1 0 B1600N HL ...
Page 96: ...96 TemBreak PRO B_BE UM 001 EN V1 1 0 Annex D Peak Let through Curves B250P ...
Page 97: ...Annex D Peak Let through Curves 97 TemBreak PRO B_BE UM 001 EN V1 1 0 B400P R ...
Page 98: ...Annex D Peak Let through Curves 98 TemBreak PRO B_BE UM 001 EN V1 1 0 B800N H G ...
Page 99: ...Annex D Peak Let through Curves 99 TemBreak PRO B_BE UM 001 EN V1 1 0 B800P R ...
Page 100: ...Annex D Peak Let through Curves 100 TemBreak PRO B_BE UM 001 EN V1 1 0 B1000N H ...
Page 101: ...Annex D Peak Let through Curves 101 TemBreak PRO B_BE UM 001 EN V1 1 0 B1250N H HL ...
Page 102: ...Annex D Peak Let through Curves 102 TemBreak PRO B_BE UM 001 EN V1 1 0 B1600N HL ...