USER INSTRUCTIONS

1) Description:

 DIN rail mountable primary switched-mode power supply with 90...264Vac (110…345Vdc) input, suitable for Single phase main line and DC line.

2) Installation:

 use DIN-rails according to EN60715. Installation should be made vertically (see Fig.4). For better device stability fix the rail to the wall close to the point where

the device is to be mounted. In order to guarantee sufficient convection, we recommend observing a minimum distance to other modules (see Fig.3).

The device is provided with a thermal protection; a limited air flow can cause the thermal protection tripping.

The SMPS automatically restarts after cooling. To get normal operation reduce the temperature of the air surrounding the power supply, increase the ventilation or reduce the

load (see Fig.8)

3) Connections

: the device is equipped with screw terminal blocks. To avoid sparks, do not connect or disconnect the connectors before having previously turned-off input

power and waited for internal capacitors discharge (minimum 1 minute)

In order to comply with UL certification, use appropriate copper cables of indicated cross section, designed for an operating temperatures of:

60°C for ambient up to 45°C

75°C for ambient up to 60°C

90°C for ambient up to 70°C

Strip the connecting ends of the wires according to the indication and ensure that all strands of a stranded wire enter the terminal connection (see Fig.5)

4) Input protection:

 the device input is provided with varistors against overvoltage. Input is provided with internal fuses 2AT/250Vac, thus an external short circuit/overcurrent

protection must be provided by the end user (see Fig.6).

For operation on a single-phase system, a protection fuse on the phase must be provided.

Surge protection:

 it is strongly recommended to provide external surge arresters (SPD) according to local regulations.

5) AC input connection:

 the device can be connected to single-phase AC lines with Uin 120…240Vac (see Fig.7).

6) DC input connection:

 connect L terminal to (+) positive pole, N terminal to (-) negative pole. Rated voltage 110...345Vdc.

The device is also suitable for photovoltaic or wind turbine applications (see Fig.7).

7) Output connection:

 The device is suitable for

SELV

 and

PELV

circuitry.

Uout can be adjusted with a potentiometer to a wide range (see Fig.1), only on Models NPSM40-515, NPSM40-12 and NPSM40-12D

Check Uout before connecting the power supply to the load. With output voltage set to the max. value, the continuous [current x voltage] must not exceed the nominal power.

8) Parallel connection and redundancy:

power supplies can be connected in parallel to increase power.

Uout must be set uniformly (±100mV) on each power supply and the wiring must be symmetrical to ensure an equal current distribution.

For redundant connection, use an external isolating device must be used (see accessory device).

9) Output protection:

 the device is protected against overload (OL) / short circuit (SC) / overvoltage (OV) / overtemperature (OT).

OL and SC:

 are controlled by a hiccup mode auto-reset protection with the following behaviour.

OL behaviour:

Max. OL = In x 1.5 with constant output voltage. If the current is

 In x 1.5 the unit enters the OL protection and starts an ON/OFF cycle (hiccup mode).

SC behaviour:

the device supplies the indicated short circuit peak current for 30ms if the output current exceeds In x 1.5 the device enters into a controlled ON/OFF cycles

(hiccup mode). The output voltage drops to a voltage value depending on the impedance of the failed load circuit.

Output OV circuit protection

: the output is protected against potential OV due to internal malfunction or coming from the load for Uout

 Unom x 1.2 – 1.3, depending on the

model.

OT protection:

 turns off the device if the internal temperature exceeds a safe limit.

The device restarts automatically after cooling down. To recover to normal operation reduce air temperature surrounding the power supply, increase cooling or reduce load

(see Fig.8).

10) Feeding DC motors:

it is possible to feed DC motors considering that when a motor starts-up under effort its consumption is much higher than the nominal current and it

can trigger overcurrent protection (see accessory device).

NOTE:

 motors can generate high conducted noise on the DC line. Therefore it is not recommended to feed on the same line motors and equipment sensitive to noise.

3

NPSM40_1680-21539-0011-E-1117

Summary of Contents for NPSM40 Series

Page 1: ...ze Plastic enclosure UL94 V0 Class II simplified wiring Overload 150 Includes 5 15V and 2 x 12 16V models Up to 50 C operating temperature with no derating INDEX Page Installation Requirements 2 Declaration of Conformity 2 User Instructions 3 Connections 4 Dimensions 4 Distances 4 Mounting 4 Dismounting 5 Input Connections 5 Environment 5 Accessory Device 5 1 NPSM40_1680 21539 0011 E 1117 ...

Page 2: ...contenitore può scottare lasciar quindi raffreddare il dispositivo prima di toccarlo Non far entrare liquidi o oggetti estranei nel dispositivo Per evitare scintille non collegare o scollegare l apparecchiatura prima di avere tolto tensione di ingresso e prima che sia avvenuta la scarica dei condensatori interni min 1 minuto RISQUE DE BRULURES EXPLOSION INCENDIE ELECTROCUTION DOMMAGE AUX PERSONNES...

Page 3: ...pole Rated voltage 110 345Vdc The device is also suitable for photovoltaic or wind turbine applications see Fig 7 7 Output connection The device is suitable for SELV and PELV circuitry Uout can be adjusted with a potentiometer to a wide range see Fig 1 only on Models NPSM40 515 NPSM40 12 and NPSM40 12D Check Uout before connecting the power supply to the load With output voltage set to the max val...

Page 4: ...gative DC 7 Common DC 8 Dimension W D H mm inc 72 2 83 61 5 2 42 90 3 54 Distance A B mm inc 10 0 4 10 0 4 Fig 4 Mounting Dismounting Instructions For DIN rail fastening according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the I S manual of each family Mount...

Page 5: ...rnal surge arresters SPD according to local regulations Fig 7 Input connections AC Line DC Line Fig 8 Environment Operating temperature Derating 40 C 70 C 5 95 r H non condensing UL Certified up to 50 C Overtemperature protection NPSM40 515 0 25W C over 50 C NPSM40 12D 0 25W C over 50 C NPSM40 12 0 35W C over 50 C NPSM40 24 0 35W C over 50 C Note Data may change without prior notice in order to im...

Page 6: ... 87 65 osman coban pewatron com Pressure Sensors Load Cells Philipp Kistler Phone 41 44 877 35 03 philipp kistler pewatron com Power supplies Sebastiano Leggio Phone 41 44 877 35 06 sebastiano leggio pewatron com Accelerometers Sensor elements Christoph Kleye Phone 49 89 374 288 87 61 christoph kleye pewatron com Harald Thomas Phone 49 89 374 288 87 23 harald thomas pewatron com Sales Other Countr...

Reviews: