USER INSTRUCTIONS

1) Description:

 DIN rail mountable primary switched-mode power supply with 90...264Vac (110…345Vdc) input, suitable for Single phase main line and DC line.

2) Installation:

 use DIN-rails according to EN60715. Installation should be made vertically (see Fig.4). For better device stability fix the rail to the wall close to the point where

the device is to be mounted. In order to guarantee sufficient convection, we recommend observing a minimum distance to other modules (see Fig.3).

The device is provided with a thermal protection; a limited air flow can cause the thermal protection tripping.

The SMPS automatically restarts after cooling. To get normal operation reduce the temperature of the air surrounding the power supply, increase the ventilation or reduce the

load (see Fig.8)

3) Connections

: the device is equipped with pluggable screw terminals. To avoid sparks, do not connect or disconnect the connectors before having previously turned-off input

power and waited for internal capacitors discharge (minimum 1 minute)

In order to comply with UL certification, use appropriate copper cables of indicated cross section, designed for an operating temperatures of:

60°C for ambient up to 45°C

75°C for ambient up to 60°C

90°C for ambient up to 70°C

Strip the connecting ends of the wires according to the indication and ensure that all strands of a stranded wire enter the terminal connection (see Fig.5)

4) Input protection:

 the device input is provided with varistors against overvoltage. Input is provided with internal fuses 3.15AT/250Vac, thus an external short

circuit/overcurrent protection must be provided by the end user (see Fig.6).

For operation on a single-phase system, a protection fuse on the phase must be provided.

Surge protection:

 it is strongly recommended to provide external surge arresters (SPD) according to local regulations.

5) AC input connection:

 the device can be connected to single-phase AC lines with Uin 120…240Vac (see Fig.7). Please connect first the PE.

6) DC input connection:

 connect L terminal to (+) positive pole, N terminal to (-) negative pole and

I

 terminal to GND. Rated voltage 110...345Vdc.

The device is also suitable for photovoltaic or wind turbine applications (see Fig.7).

7) Output connection:

 The device is suitable for

SELV

 and

PELV

circuitry.

Uout can be adjusted with a potentiometer to a wide range (see Fig.1)

Check Uout before connecting the power supply to the load. With output voltage set to the max. value, the continuous [current x voltage] must not exceed the nominal power.

8) Parallel connection and redundancy:

power supplies can be connected in parallel to increase power. For paralleling for power set the Ilim jumper to C.C. algorithm.

Uout must be set uniformly (±100mV) on each power supply and the wiring must be symmetrical to ensure an equal current distribution.

Models with

“P”

 suffix have an integrated ORing circuit.

For redundant connection, use the Models

“P”

 or an external isolating device must be used (see accessory device).

9) Output protection:

 the device is protected against overload (OL) / short circuit (SC) / overvoltage (OV) / overtemperature (OT).

OL and SC:

 are controlled by a hiccup mode or a constant current (C.C.) mode protection with the following behaviour.

The Hiccup mode or C.C. mode are selectable with Jumper (see Fig.1)

OL behaviour in hiccup mode:

 Max. OL = 1.5 x In the output voltage remains constant at nominal voltage for 5s and after that time the device starts an ON/OFF cycle.

OL behaviour in C.C. mode:

the maximum output current is limited at 1.5 x In if the load resistance is further decreased the output voltage starts to drop.

SC behaviour in hiccup mode:

 the device supplies 1.5 x In for 5s, after that time it switches off for 10s. The ON/OFF cycle is repeated continuously.

SC behaviour in C.C. mode:

 the device supplies 1.5 x In the output voltage drops to a value depending on the impedance of the failed load circuit. After 5s the current is

limited to In. The device never switches off.

Output OV circuit protection

: the output is protected against potential OV due to internal malfunction or coming from the load for Uout

 Unom x 1.2 – 1.3, depending on the

model.

OT protection:

 turns off the device if the internal temperature exceeds a safe limit.

The device restarts automatically after cooling down. To recover to normal operation reduce air temperature surrounding the power supply, increase cooling or reduce load

(see Fig.8).

10) Feeding DC motors:

it is possible to feed DC motors considering that when a motor starts-up under effort its consumption is much higher than the nominal current and it

can trigger overcurrent protection (see accessory device). For these applications the C.C. (Constant Current) mode of current limitation is recommended.

NOTE:

 motors can generate high conducted noise on the DC line. Therefore it is not recommended to feed on the same line motors and equipment sensitive to noise.

11) Operation with Battery:

 when a battery is connected in parallel to the Output for backup purposes; the NPSM121 must be set on C.C. mode to avoid battery over-charging

(see accessory device).

Summary of Contents for NPSM121 Series

Page 1: ...l efficiency Overload 150 Up to 60 C operating temperature with no derating Constant current or Hiccup mode limitation user settable Wide range of output voltage Easy parallelable for power increase Only 35mm width aluminum enclosure INDEX Page Installation Requirements 2 Declaration of Conformity 2 User Instructions 3 Connections 4 Dimensions 4 Distances 4 Mounting 4 Dismounting 5 Input Connectio...

Page 2: ...ispositivo prima di toccarlo Non far entrare liquidi o oggetti estranei nel dispositivo Per evitare scintille non collegare o scollegare l apparecchiatura prima di avere tolto tensione di ingresso e prima che sia avvenuta la scarica dei condensatori interni min 1 minuto RISQUE DE BRULURES EXPLOSION INCENDIE ELECTROCUTION DOMMAGE AUX PERSONNES Ne jamais effectuer des opérations sur les parties sous...

Page 3: ...upply to the load With output voltage set to the max value the continuous current x voltage must not exceed the nominal power 8 Parallel connection and redundancy power supplies can be connected in parallel to increase power For paralleling for power set the Ilim jumper to C C algorithm Uout must be set uniformly 100mV on each power supply and the wiring must be symmetrical to ensure an equal curr...

Page 4: ...gative DC I earth ground Output Positive DC Negative DC Dry contact NC Dimension W D H mm inch 35 1 37 104 4 09 103 4 05 Distance A B mm inch 20 0 8 50 2 0 Fig 4 Mounting Dismounting Instructions For DIN rail fastening according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices as...

Page 5: ... SPD according to local regulations Fig 7 Input connections AC Line DC Line Fig 8 Environment Operating temperature Derating 35 C 70 C 5 95 r H non condensing UL Certified up to 60 C Overtemperature protection 1 2W C over 60 C Note Data may change without prior notice in order to improve the product Please refer to the latest version of the Instruction Manual for each product by visiting www nexty...