1. Important Safety Warning 

Please comply with all warnings and operating instructions in this manual strictly. Save this 
manual properly and read carefully the following instructions before installing the unit. Do not 
operate  this  unit  before  reading  through  all  safety  information  and  operating  instructions 

carefully 
 

1-1. Transportation 

 

Please transport the UPS system only in the original package to protect against shock 
and impact. 

 

1-2. Preparation 

 

Condensation may occur if the UPS system is moved directly from cold to warm 
environment. The UPS system must be absolutely dry before being installed. Please 
allow at least two hours for the UPS system to acclimate the environment.   

 

Do not install the UPS system near water or in moist environments. 

 

Do not install the UPS system where it would be exposed to direct sunlight or near 
heater. 

 

Do not block ventilation holes in the UPS housing. 

 

1-3. Installation 

 

Do not connect appliances or devices which would overload the UPS system (e.g. 
laser printers) to the UPS output sockets.   

 

Place cables in such a way that no one can step on or trip over them.   

 

Do not connect domestic appliances such as hair dryers to UPS output sockets.   

  The UPS can be operated by any individuals with no previous experience. 

 

 

Connect the UPS system only to an earthed shockproof outlet which must be easily 
accessible and close to the UPS system.   

 

Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your 
computer) to connect the UPS system to the building wiring outlet (shockproof 
outlet).   

 

Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS 
system.   

 

When installing the equipment, it should ensure that the sum of the leakage current 
of the UPS and the connected devices does not exceed 3.5mA. 

 

1-4. Operation 

 

Do not disconnect the mains cable on the UPS system or the building wiring outlet 
(shockproof socket outlet) during operations since this would cancel the protective 
earthing of the UPS system and of all connected loads.   

 

The UPS system features its own, internal current source (batteries). The UPS output 
sockets or output terminals block may be electrically live even if the UPS system is not 
connected to the building wiring outlet.   

 

In order to fully disconnect the UPS system, first press the OFF/Enter button to 
disconnect the mains.   

 

Prevent no fluids or other foreign objects from inside of the UPS system.   

 

Summary of Contents for MANTIS 1100 RT

Page 1: ...www nextups eu Line Interactive Sinewave UPS MANTIS 1100 RT MANTIS 1500 RT MANTIS 2000 RT MANTIS 3000 RT Uninterruptible Power Supply System User Manual...

Page 2: ...Rear Panel View 4 2 2 Install The UPS 4 2 3 Setup The UPS 5 2 4 Battery Replacement 7 2 5 Battery Kit Assembly option 8 3 Operations 10 3 1 Button Operation 10 3 2 LCD Panel 10 3 4 LCD Display Wordin...

Page 3: ...trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an ea...

Page 4: ...persons must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals...

Page 5: ...4 Input circuit breaker 5 Network Fax Modem surge protection 6 Emergency power off function connector EPO 7 USB communication port 8 RS 232 communication port 9 SNMP intelligent slot 10 External batte...

Page 6: ...l devices by setting shorter backup time for non critical devices Step 3 Communication connection Communication ports USB port RS 232 port Intelligent slot To allow for unattended UPS shutdown start u...

Page 7: ...ted external battery boxes up to 4 units Step 7 Turn on the UPS Press the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hou...

Page 8: ...s and notes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the batte...

Page 9: ...rt Step 3 Put assembled battery packs on one side of plastic shells and insert one more defect battery on the space Step 4 Cover the other side of plastic shell as below chart Then battery kit is asse...

Page 10: ...dhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart...

Page 11: ...TER Button Turn off the UPS Press and hold this button at least 2 seconds to turn off the UPS Confirm selection key Press this button to confirm selection in UPS setting mode SELECT Button Switch LCD...

Page 12: ...information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuited UPS status Indicates that programmable management outlets...

Page 13: ...e outlets setting LCD display direction and exit 01 Output voltage setting Interface Setting For 208 220 230 240 VAC models you may choose the following output voltage 208 presents output voltage is 2...

Page 14: ...for setting programmable outlet Step 1 Before entering setting mode the UPS should be in Stand by mode off charging and make sure the battery is connected The LCD display is shown as right Step 2 Pres...

Page 15: ...iption LCD display ECO mode When the input voltage is within voltage regulated range UPS will power the output directly from the mains ECO is an abbreviation of Efficiency Corrective Optimizer In this...

Page 16: ...too low 28 Inverter soft start fail 11 x Over temperature 41 x Inverter voltage high 12 x Over load 43 Inverter voltage Low 13 x 3 8 Warning Indicator Warning Icon flashing Alarm Low Battery Sounding...

Page 17: ...y second The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously...

Page 18: ...tery backup time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batte...

Page 19: ...t your dealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage...

Page 20: ...V 9 Ah x4 12 V 9 Ah x6 Charging Voltage 27 4 VDC 1 54 8 VDC 1 82 1 VDC 1 Recharge Time 4 hours recover to 90 capacity PROTECTION Full Protection Overload short discharge and overcharge protection ALAR...