5.
COOLER AND CONTROLLER TROUBLESHOOTING TIPS
5.1
RSF Alarms
Refrigeration system failure (rSF) alarms trigger if the set point (SP) temperature is not reached within the
time defined by the compressor runtime (Ct) parameter.
The controller has detected a problem with the cooling system, please check:
`
Electrical connection from the output of the controller to the compressor
`
Compressor circuit failure (including fuse protection if fitted)
`
Adequate airflow through condenser – Condenser grill is free from obstructions
`
Condenser fan operation
`
If there is Refrigeration System leakage
5.2
Door Switch Broken Alarms
The controller has detected a problem with the door switch input, please check:
`
The door of the cooler is fully closed and able to be fully closed after each opening
`
The door switch is properly connected to the door switch input on the controller
`
The door switch is in working order – The door switch should read short circuit when a
magnet is placed next to the door switch.
`
The door switch input on the controller is in working order – The controller should only
register door open (do) when an open circuit is seen on the door switch input
5.3
Door Broken Alarms
The controller has detected a problem with the door, please check:
`
The door of the cooler is fully closed and able to be fully closed after each opening
`
The door switch is properly connected to the door switch input on the controller
`
The door switch is in working order – The door switch should read short circuit when a
magnet is placed next to the door switch.
`
The door switch input on the controller is in working order – The controller should only
register door open (do) when an open circuit is seen on the door switch input
5.4
Appliance Sensor Alarms
The controller has detected an open circuit on the appliance input, please check:
`
The appliance sensor is properly connected to the appliance input on the controller
`
The appliance sensor is reading the correct temperature – Temperature versus resistance:
Thermistor is Negative Temperature Coefficient (NTC)
`
The appliance input on the controller is in working order – The controller should not register a
PF1 alarm when a known working appliance sensor is connected