TROUBLESHOOTING
SYMPTOM
CAUSE
CURE
Sensor fails to add to the
network (slow blinking of the
Status LED and no pairing
action seen on the bridge)
Out of range
Add a Z-Wave repeating device (e.g. light module/dimmer) at a location between the bridge and
the sensor.
1. Add a repeater to the network following that device’s instructions.
2. Try to add the sensor to the network again at the desired sensing location.
Improperly removed from
network previously
1. Remove the sensor from the network following the steps in the “REMOVE” table.
2. Try to Add the sensor to the network.
Sensor drops connection
intermittently
Edge of range
Add a Z-Wave repeating device (e.g. light module/dimmer) at a location between the bridge and
sensor.
Button press ignored
Button press too fast or
too slow
Use firm ½ second button press.
FACTORY RESET
Factory Reset should only be used when the primary controller is missing or otherwise inoperable.
Press and hold, approximately 10 seconds, until the STATUS LED starts blinking to restore factory defaults.
ASSOCIATION GROUP INFORMATION TABLE
Group
Profile
Command Classes
Group Name
Max Devices
1
Lifeline
Battery Report, Multilevel Sensor Report, Device Reset
Locally Notification
Lifeline
1
2
Sensor
Multilevel Sensor Report
Temperature Reports
5
3
Sensor
Multilevel Sensor Report
Humidity Reports
5
4
Sensor
Basic Set
Temperature Driven Basic Sets
5
5
Sensor
Basic Set
Humidity Driven Basic Sets
5
6
Sensor
Battery Report
Battery Reports
5
Z-WAVE CONFIGURATION TABLE
Parameter
Description
Length
(Bytes)
R/W
Default
Value
Valid Values
1
Time between Battery Reports (hours)
1
R/W
0
0 = Do not send periodically; Range: 1–127 hours
2
Send BASIC SET ON above this temperature (See #20)
1
R/W
121
121 = Disabled; Range: 15 – 120° F
3
Send BASIC SET ON below this temperature (See #20)
1
R/W
121
121 = Disabled; Range: 15 – 120° F
4
Send BASIC SET OFF above this temperature (See #20)
1
R/W
121
121 = Disabled; Range: 15 – 120° F
5
Send BASIC SET OFF below this temperature (See #20)
1
R/W
121
121 = Disabled; Range: 15 – 120° F
6
Send multiple attempts for all BASIC SET commands
1
R/W
0
0 = Disabled; 1-5 = Number of extra attempts sent
every minute after first send
7
Temperature Units
1
R/W
1
1 = Fahrenheit; 0 = Celsius
8
Association Group1 – Temperature delta auto send threshold
1
R/W
10
Range: 1 – 200; Parameter is in tenths of degrees.
9
Association Group1 – Periodic temperature send interval
1
R/W
0
0 = Disabled; Range: 1-120 minutes
10
Association Group2 – Temperature delta auto send threshold
1
R/W
10
0 = Disabled; Range: 1 - 50
Parameter is in tenths of degrees.
11
Association Group2 – Periodic temperature send interval
1
R/W
0
0 = Disabled; Range: 1-120 minutes
12
Send BASIC SET ON above this humidity (See #20)
1
R/W
0
0 = Disabled; Range: 1-100%
13
Send BASIC SET ON below this humidity (See #20)
1
R/W
0
0 = Disabled; Range: 1-100%
14
Send BASIC SET OFF above this humidity (See #20)
1
R/W
0
0 = Disabled; Range: 1-100%
15
Send BASIC SET OFF below this humidity (See #20)
1
R/W
0
0 = Disabled; Range: 1-100%
16
Association Group1 – Humidity delta auto send threshold
1
R/W
5
Range: 1-50%
17
Association Group1 – Periodic humidity send interval
1
R/W
0
0 = Disabled; Range: 1-120 minutes
18
Association Group3 – Humidity delta auto send threshold
1
R/W
5
0 = Disabled; Range: 1-30%
19
Association Group3 – Periodic humidity send interval
1
R/W
0
0 = Disabled; Range: 1-120 minutes
20
BASIC SET options for temperature and humidity
1
R/W
1
Configuration Register Combinations:
1 = Enable Registers 2, 5, 12 15
2 = Enable Registers 2, 5, 13, 14
3 = Enable Registers 3, 4, 12, 15
4 = Enable Registers 3, 4, 13, 14
21
Temperature Offset
1
R/W
0
Range: -7 to 7° F
22
Humidity Offset
1
R/W
0
Range: -7 to 7%
23
Humidity Filter Time Constant
1
R/W
30
Range: 1 – 60 minutes