4
DB6.3
DB6.0
Not used
Not used
Not used
Example:
Raw Frame: A2050000703790
Decoded frame:
-
Type of product: 0xA2 -> Origin Lora
-
Type of message: 0x05 -> Real Time
-
IAQ_Global: 0x0 -> Excellent
-
IAQ_Source: 0x0 -> All
-
IAQ_Dry: 0x0 -> Excellent
-
IAQ_Mould: 0x0 -> Excellent
-
IAQ_Dust_Mites: 0x0 -> Excellent
-
Temperature : 0xE0 -> 22.4°C
-
Relative Humidity : 0x6F -> 55.5 %RH
-
Frame index: 0x1 -> Frame index 1
4.7 Datalog Temperature
The oldest data are referred to [n-x-1]
, …
,[n-2], [n-1] then [n] (x refer to the number of data contained
in the frame). The data [n] corresponds to current data.
Example: in the case of a configuration with a 30-minute period between the measurements:
If the message is received at noon, the corresponding hours are the following:
-
Measurement [n-11]: 6h30
-
Measurement [n-10]: 7h
-
Measurement [n-9]: 7h30
-
Measurement [n-8]: 8h
-
Measurement [n-7]: 8h30
-
Measurement [n-6]: 9h
-
Measurement [n-5]: 9h30
-
Measurement [n-4]: 10h
-
Measurement [n-3]: 10h30
-
Measurement [n-2]: 11h
-
Measurement [n-1]: 11h30
-
Measurement [n]: 12h