IMPORTANT NOTES :
- Euromold bushings are supplied with protective caps over the mating interface offering protection against mechanical damage and the ingress
of any contaminant. Under no circumstances should this shipping cap be considered as an electrical dead-ending device.
- Euromold bushings should never be energised in isolation neither should they be disconnected whilst energised. They should always be
connected to one of the recommended mating parts or the electrical dead-ending device : 4000DR, K400DR, M400DR, 400DR/G, K400DR/G
or
M400DR/G.
- Do not paint the interface.
- Fixing devices are not supplied.
Tighten nuts using a key of 17 mm.
Tightening torque : 16 Nm
(1,6 kgm or 11,6 Foot-pounds).
IS 400AR-8-E
Page 2 of 2