Nexans 400AR-8 Installation Instructions Download Page 2

IMPORTANT NOTES :

-  Euromold bushings are supplied with protective caps over the mating interface offering protection against mechanical damage and the ingress 
  of any contaminant. Under no circumstances should this shipping cap be considered as an electrical dead-ending device.

-  Euromold bushings should never be energised in isolation neither should they be disconnected whilst energised. They should always be  
  connected to one of the recommended mating parts or the electrical dead-ending device : 4000DR, K400DR, M400DR, 400DR/G, K400DR/G 
 or 

M400DR/G.

-  Do not paint the interface. 

-  Fixing devices are not supplied.

Tighten nuts using a key of 17 mm.

Tightening torque : 16 Nm

(1,6 kgm or 11,6 Foot-pounds).

IS 400AR-8-E
Page 2 of 2

Nexans Network Solutions NV - div. EUROMOLD 

Zuid III - Industrielaan 12

B-9320 EREMBODEGEM-AALST  –  BELGIUM

Tel: +32 (0)53/85 02 11 – Telefax: +32 (0)53/83 10 13

a Nexans company

M10

(K),(M)400AR-8/GS equipment

bushing with earthing plate

Typical fixing with

Claw Clamps

NF C 52-053

(K),(M)400AR-8/J equipment

bushing with earthing jumper

 bushing screen

 earth connection
(earthing jumper)

equipment 

connection

4 x stud M10

equipment

protective cap

bushing interface

clamp

NF C 52-053

gasket

 tabs for

 bail restraint

bushing screen

earth connection

(earthing plate)

clamp

NF C 52-053

OIL

LEVEL

Dia. 126