![Nexans 400AR-8 Installation Instructions Download Page 1](http://html.mh-extra.com/html/nexans/400ar-8/400ar-8_installation-instructions_1681148001.webp)
min.
55
M10
Dia. 78
Dia. 123
max.
20
(K)(M)400AR-8
This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. These instructions are not intended as a
substitute for adequate training or experience in such safety practices. These instructions do not attempt to provide for every possible contingency.
Failure to follow these instructions could result in damage to the product and serious or fatal injury.
IMPORTANT : Cable and associated apparatus must be de-energised, locked out, and tagged prior to product installation.
91
04
2E-
R/2
IS 400AR-8-E
Page 1 of 2 - 12 February 2010
Supersedes edition of 3 February 2010
M10
bushing interface
equipment
connection
4 x stud M10
equipment
protective cap
A DIN 42 538
fixing flange
bushing screen
earth connection
(earthing jumper)
tabs for
bail restraint
flexible connection
Typical fixing with ring clamp DIN 42 538
IMPORTANT NOTES :
- Euromold bushings are supplied with protective caps over the mating
interface offering protection against mechanical damage and the ingress of
any contaminant. Under no circumstances should this shipping cap be
considered as an electrical dead-ending device.
- Euromold bushings should never be energised in isolation neither should
they be disconnected whilst energised. They should always be connected
to one of the recommended mating parts or the electrical dead-ending
device : 4000DR, K400DR, M400DR, 400DR/G, K400DR/G or M400DR/G.
- Do not paint the interface.
- Fixing devices are not supplied.
Installation Instructions
Equipment Bushings - Type B interface
250 A - Up to 36 kV
CAUTION : Read instructions thoroughly and completely prior to beginning installation.
Tighten nuts using a key of 17 mm.
Tightening torque : 16 Nm
(1,6 kgm or 11,6 Foot-pounds).
OIL
LEVEL
a Nexans company
E DIN 42 538
clamp
(K),(M)400AR-8/J equipment
bushing with earthing jumper
gasket
!
!
FOR INFORMATION ONLY
Please always use the
instruction supplied
in the kit