NewMar PM-24-80 Installation And Operation Manual Download Page 4

P.O. Box 1306, Newport Beach, California 92663  •  Phone: 714-751-0488  •  Fax: 714-957-1621  •  E-Mail: [email protected]

www.newmartelecom.com

4

P.O. Box 1306, Newport Beach, California 92663  •  Phone: 714-751-0488  •  Fax: 714-957-1621  •  E-Mail: [email protected]

www.newmartelecom.com

III) INSTALLATION

A) Materials Provided

Prior to installation, check to ensure that each of the following items 

have been included with the packaging. For any missing items 

please contact the factory or warehouse.

(2) ea. mounting brackets for 19” rack mounting

(2) ea. mounting brackets for 23” rack mounting

(6) ea. 6-32 X 3/8” pan head phillips screws, black

(1) ea. Molex “pigtail” connector

(1) ea. Installation/Operation manual

(1) ea. Customer Satisfaction/Warranty card

(1) ea. Output Terminal Cover

B) Mounting

The PM is designed for various mounting options. Hardware for 19” 

or 23” rack mounting is included

The PM is provided with two sets of mounting brackets and six 6-32 

x 3/8” pan head phillips screws for attaching the brackets to the 

PM chassis. Select the appropriate bracket set for the 19” or 23” rack 

and fasten to the PM. Bracket attachment holes in the PM chassis 

are provided to allow for 6” forward mounting only. 

C) A.C. Input Wiring

Input Voltage: 

the PM is designed to accept 207-253 VAC, 50/60 

HZ, single phase input.

FIGURE 3: a.c. Input Wiring Compartment (PM rear view; 

2,500 watt series)

1) Replace the input wiring cover.

Important: Although the internal a.c. wiring is protected by the 

front panel mounted circuit breaker, the wiring to the PM must also 

be protected by wiring to an appropriate circuit breaker (30 Amp 

double pole recommended for Line-Line AC sources).

D) D.C. Output Wiring

Important: Ensure that a.c. input to the PM is switched off before 

working with d.c. wiring. The output terminals are “hot” whenever 

the unit is switched on.

1) Output bus for hard-wiring of DC output are located on the rear 

panel of the PM. Terminate wires with 1/4” ring lug connectors for 

a secure installation. (Note:  Output bus will accommodate 2 hole 

lugs, 3/4” or 1” hole centers)

2) Use the chart below to determine minimum gauge for wires 

depending on the particular model and the length of the run from 

the PM to the load or distribution bus (or refer to N.E.C or local 

codes for any questions regarding proper d.c. wire gauges).

D.C. Wire Size Table:
Model Minimum Wire Size per N.E.C. AWG (mm)

PM-48-50 #8 (10 mm)

PM-24-80 #4 (25 mm)

Summary of Contents for PM-24-80

Page 1: ...D EMI COMPATIBILITY 3 B EMI Electro magnetic Interference 3 C Other Factors 3 III INSTALLATION 4 A Materials Provided 4 B Mounting 4 C AC Input Wiring 4 D DC Output Wiring 4 E Parallel Wiring 5 F Chas...

Page 2: ...and rear panel features of the Power Modules are illustrated below along with the page number where information on each particular feature is located FAX 714 957 1621 TEL 714 751 0488 techservice new...

Page 3: ...an range from 1 to 100 times the normal AC voltage level and can last for a fraction of a cycle to a few cycles Transient disturbances can be placed into two categories Lightning generated Equipment g...

Page 4: ...PM Bracket attachment holes in the PM chassis are provided to allow for 6 forward mounting only C A C Input Wiring Input Voltage the PM is designed to accept 207 253 VAC 50 60 HZ single phase input F...

Page 5: ...tage If adjustment is necessary use a small at tip screwdriver to turn the OUTPUT VOLTAGE ADJUST potentiometer on the front panel until the voltmeter reads the desired system output voltage 4 Shut off...

Page 6: ...ber e g PM 48 50 is rated at 50 amps continuous duty To prevent overload when recharging severely discharged batteries current is limited at approximately 105 of the continuous duty rating by a curren...

Page 7: ...he rear panel which secure the top cover Remove the two screws on the sides near front which secure top cover 3 Locate the two fans located on one end of the main circuit board near the rear of the PM...

Page 8: ...C 48 v model or 60 mV per C 24 v model If the battery reaches 50 C the PM will turn itself off The PM will automatically restart once the battery temperature drops approximately 5 10 C Temperature Pr...

Page 9: ...er con rm AC input or is not receiving correct input voltage voltage Check input connections 2 PM limiting its output due to overload 2 Reduce DC load and or determine or ambient over temperature cond...