NewMar DST-20A Installation & Operation Instructions Download Page 4

4

15272 Newsboy Circle
Huntington Beach
California 92649

                              

  

Phone:  714-751-0488  

                                     Fax: 714-856-9679 

     E-Mail: [email protected]

PoweringTheNetwork.com

B) Breaker Removal

The front panel must be removed in order to remove any breaker. 
It is not necessary to remove the toggle guard in order to remove 
the front panel.

A special extraction tool (with screws) has been provided to 
facilitate breaker removal without putting unnecessary lateral 
stress on the internal sockets and mating clips. Screw the breaker 
extraction screws part way in, then use the tool to pull the breaker 
firmly out (as shown in FIGURE 2).

FIGURE 2: Circuit Breaker Extraction

C) Remote Summary Alarm Wiring

A connector at the rear of the panel enables optional installation 
of a remote summary alarm to indicate when any breaker has 
been over-current tripped. Separate contacts are provided for 
each bus to activate Bus A and Bus B alarms independently, if 
desired (Bus A only for model DST-10). The alarm contacts are 
configured Normally Open (N.O.) and close when a breaker is 
tripped (not when shut off manually—see Circuit Breaker Function 
section). Diagrams on each side of the connector (labeled 
“BREAKER STATUS”) in the center of the rear panel illustrate the 
contactor positions when any breaker in the bus is in a TRIPPED 
state.

A 35" four wire connector harness is provided for remote alarm 
indication (two wires for each bus). One of two different versions 
have been supplied:

1)

 Orginal version: Molex connectors at both ends for compatible

connection with the earlier PMF-400 Power Function Manager 
(LVD, Digital Meter: volts/amps, load distribution, alarms). For 
application not involving a PFM-400, clip-off one of the connectors 
and use parallel splices and 18 AWG wire to connect the DST 
alarm contacts to your monitoring system.

2) 

Later version: Molex connector on one end and pigtail on 

opposite end.

PFM-400 Wiring:

 For version 1 alarm harness, plug one end of the 

harness into the keyed connector on the rear of the DST which is 
labeled BREAKER STATUS. Note, the harnes is reversible, therefore 
it does not matter which end is plugged in. Plug the other end into 
an unused STATUS CONTACT INPUT connector on the rear of the 
PFM. (Typically, the #5/#6 connector will be used when Power 

Modules are connected to the PFM, but the summary alarm will 
function the same in either the #1/#2 or #3/#4 connector positions, 
as well).

PFM-500 Wiring:

 For version 2 alarm harness, plug the connector 

end of the harness into the keyed connector on the rear of the DST 
which is labeled 'BREAKER STATUS'. The pigtail end can be wired 
to an unused STATUS CONTACT input on the rear panel of the 
PFM-500; connect the Blue and Yellow wires (DST-10) to terminals 
#1 and #3. For a DST-20A, parallel Brown and Blue wires and 
connect to terminal 1 and parallel Orange and Yellow wires and 
connect to terminal #3.

If all STATUS CONTACT positions are occupied (PFM-400) or wired 
(PFM-500) (i.e., five or six Power Modules are in the system), 
and a summary alarm from the DST is required, this may be 
accomplished through parallel wiring of the status wires. Please 
contact the factory for information on how to perform this 
modification.

Note:

 Although the breaker status contacts in the DST operate in 

a Normally Open configuration, the summary alarm contacts 
within the PFM are Form C; that is, the connector labeled OUTPUT 
SUMMARY ALARM on the rear of the PFM may be wired in either 
Normally Open or Normally Closed configuration.

When wired to the PFM in this fashion any tripped breaker within 
the DST will result in illumination of the CHECK SYSTEM light on 
the front of PFM, as well as activation of the PFM summary alarm 
contacts. For additional information on PFM operation, refer to the 
manual provided with that product.

Caution:

 Status contact wiring cannot be paralleled in 

applications where the A and B buses are of different voltages or 
have a different ground reference.

Power through the alarm contacts must not exceed the following:
1 amp @ 125 VAC
5 amps @ 30 VDC

VI) CIRCUIT BREAKER FUNCTION

The plug-in circuit breaker functions as an on/off load switch and 
provides over-current protection specified by its amperage rating. 
However, the special mid-trip feature enables the technician to 
distinguish between a condition where the breaker has been 
tripped by over-current and where it has been intentionally 
shut off.

When the circuit breaker is manually shut off, the alarm contacts 
within the DST will remain in the “OPEN” position, to avoid setting 
off alarms unnecessarily when load disconnect is intentional. 
When the breaker is over-current tripped, the toggle will rest at a 
90 degree position (for easy identification of the tripped circuit), 
and the alarm contacts will be in the “CLOSED” position. To reset, 
(after the overload condition has been corrected) simply switch 
the breaker off and back on again. To test the alarm, place a PBA 
breaker in the 'ON' position and slam the bottom of the breaker 

Plug-In Breaker

Extraction Tool

Breaker 

Extraction 

Screws

Summary of Contents for DST-20A

Page 1: ...EL INSTALLATION 3 A Panel Mounting B Input Wiring C Output Load Wiring V CIRCUIT BREAKER AND SUMMARY ALARM INSTALLATION 3 A Breaker Installation B Breaker Removal C Remote Summary Alarm Wiring VI CIRC...

Page 2: ...s Warranty period for the panel is two years parts and labor For questions or comments on Newmar Distribution Panels please call 800 854 3006 or e mail sales newmarpower com II IMPORTANT SAFETY INFORM...

Page 3: ...A ten are provided with model DST 10 Use of any of the outputs requires installation of a plug in breaker at that position Outputs 1 10 are fed by BUS A only outputs 11 20 are fed by BUS B only unless...

Page 4: ...g For version 2 alarm harness plug the connector end of the harness into the keyed connector on the rear of the DST which is labeled BREAKER STATUS The pigtail end can be wired to an unused STATUS CON...

Page 5: ...s are provided for each bus on model DST 20A A and B status contact wiring cannot be paralleled in applications where the buses are at different voltages or ground reference Maximum power through the...

Page 6: ...INCLUDED RETURN HOT GROUND RETURN GROUND HOT TO BUS B LOAD CHASSIS GROUND BUS B HOT SOURCE BUS A HOT SOURCE DST 20A SHOWN AS VIEWED FROM WIRING SIDE SPLIT BUS INSTALLATION MODEL DST 20A ONLY UP TO 10...

Page 7: ...marpower com PoweringTheNetwork com XII OUTLINE AND MOUNTING DRAWING 82 1 00 312 X 500 SLOT 312 63 TYP 1 4 20 PRESS IN NUT TYP ROTATED VIEW 1 1 1 1 1 1 14 10 56 8 56 2X 6 00 3 47 17 00 8X 25 2X 3 00 2...

Reviews: