NewMar DCV Installation & Operation Manual Download Page 2

Phone: 714-751-0488

Fax: 714-957-1621

E-Mail: [email protected]

P.O. Box 1306
Newport Beach,
California 92663

FIGURE 3

Carefully check all your wiring against that shown in
FIGURES 2 and 3.  If everything is wired correctly you can
mount the DCV in the instrument hole. Be sure the bulkhead
gasket is in place and use only finger tension to tighten the
bracket hold-down nuts. 

Do not overtighten the bracket or

you may damage the case 

do not use tools to tighten the

nuts.

Operation

Key Functions

The                                             keys are used to select what to
display, backlights, calibrate volts/amps, turn alarms on/off,
and set alarms values. New information is automatically
saved to memory.

Turning Alarms ON/OFF

Press the

key 1/2 second to turn alarms ON.  The Battery

(1, 2, or 3) icon will blink.  Press the 

 key 1/2 second to

turn the alarms OFF.

Backlight Intensity

Press 

the key 1/2 second to adjust the backlight level for

night-time viewing.  Each time you press the 

 key 1/2

second, the level will get brighter 1, 2, 3, 4, OFF, 1, 2...etc.
Screw terminal pin (D) must be switched on for the backlights
to work.

Display Volts for Battery 1, 2, or 3

Quick press one of the                                            keys to select
Battery 1, 2, or 3.

Setting High Volts Alarm

Select the battery (1, 2, or 3) for which you wish to set the

High Volts Alarm. Press and hold the 

key for ten (10)

seconds.  You will hear a beep and the High Volts alarm value

for that battery will be displayed.   Use the 

and 

keys

to set the desired alarm value.   Press the 

 key to save the

High Volts Alam value to memory.

Setting Low Volts Alarm

Select the battery (1, 2, or 3) for which you wish to set the

Low Volts Alarm. Press and hold the

key for ten (10)

seconds.  You will hear a beep and the Low Volts alarm value

for that battery will be displayed.  Use the 

and 

keys

to set the desired alarm value.   Press the

key to save the

new alarm value.

Calibrating the Instrument

The DCV is calibrated at time of manufacture for 12V battery
banks, but can be calibrated at any time by using the front
panel keys. Battery 1, 2, or 3 can be independently calibrated.
To calibrate the voltmeter, press and hold down one of the

keys for three seconds (to calibrate battery 1, 2, or 3) while

applying power to the instrument.  Use the 

and 

keys

to make the displayed value read correctly. Press the

key

to save the calibration data to memory.

Selecting NMEA 0183 or External Alarm Output

The DCV comes factory pre-set to output NMEA 0183
compatible serial data. If you do not need this feature or
would rather have an external alarm output on screw terminal
(C), you can do so as follows.

While viewing battery voltage (any battery), press and hold

down both the

and 

 

keys for 10 seconds (until you

hear a long beep).  This operation switches the output mode
between NMEA 1083 and External Alarm. The new output
mode is automatically saved to memory.

When the external alarm output is activated, a 5V signal (10
mA Max.) is output on screw terminal (C).

1

2

3

1

2

3

1

2

3