34
FIG 24 TROUBLESHOOTING CHART – continued
PROBLEM
CAUSE
CORRECTION
Firing Rate Too Low
Use Higher Input Nozzle
Dirty Heat Exchanger
Clean Heat Exchanger
Poor Combustion
Adjust Using Instruments
Undersized Capacity
Size Based on Heat Loss
Distribution System
Ensure Proper Design
Not Enough Heat
Faulty Thermostat or Location
Repair, Replace, or Relocate
Defective Primary Control
Repair or Replace
Faulty Thermostat or Location
Repair, Replace, or Relocate
Faulty Oil Pump
Check for Proper Pressure
Firing Rate Too High
Reduce Nozzle Size
Oversized Capacity
Size Based on Heat Loss
Too Much Heat
Distribution System
Proper Duct Design
Poor Combustion
Adjust Using Instruments
Excess Air
Adjust Air Setting
Inadequate Flue Draft
Provide Specified Draft
Insufficient Combustion Air
Provide Combustion Air
Oil Supply
Check Oil Supply
Electrode Setting
Adjust Electrodes
Wrong Nozzle
Use Specified Nozzle
Fuel System Leaking
Check Fuel System
Excessive Oil Consumption
Faulty Oil Pump
Repair or Replace Pump
Over-Firing
Use Specified Nozzle Size
Replace Dirty Filters
Increase Blower Speed
Increase Undersized R/A Ducts
Clear Blocked Return Registers
Increase Undersized S/A Ducts
Clear Blocked Supply Grills
Replace Faulty Blower Motor
Clean Clogged Blower Wheel
Tripping High Limit
Replace Broken Blower Belt
Faulty Thermostat or Location
Repair, Replace, or Relocate
Heat Anticipator Set Too Low
Adjust Heat Anticipator
Short Cycle
Defective Primary Relay
Repair or Replace Relay
Burner Pump Whine
Eliminate Suction Line Air Leak
Duct Expansion
Stiffen Plenum & Ducts
Noise
Plenum Amplifies Noise
Install Plenum Apron
Blocked Flue Passages
Clean Boiler
Unspecified Burner
Replace Burner
Unspecified Nozzle
Install Correct Nozzle
Incorrect Head
Install Correct Head
Wrong/Misaligned Static Plate
Install Correct Plate or Align
Chimney Down Drafting
Install Chimney Cap
Increase Draft at Breech
Poor Over-Fire Draft
Correct Chimney Problems
Use Specified Nozzle
Over-Firing
Use Specified Pressure
Use Correct Air Tube Assembly
Burner Air Tube Burn-Off
Incorrect Insertion
Adjust Flange
Reduced Draft
Add Combustion Air
Delayed Ignition
Adjust Burner Settings
Loss of Prime
Eliminate Teed Oil Lines
Unspecified Burner
Replace Burner
Unspecified Nozzle
Install Correct Nozzle
Frequent Sooting
Incorrect Head
Install Correct Head
Reduce Motor Speed
Premature Corrosion
Temperature Rise Too Low
Use Higher Specified Nozzle
Summary of Contents for LFR-72
Page 17: ...16 FIG 10 TYPICAL OIL TANK PIPING INSTALLATIONS...
Page 18: ...17 FIG 11 DIMENSIONS CONTROL LOCATION NH3...
Page 19: ...18 FIG 12 LFR SET UP...
Page 20: ...19 FIG 13 STANDARD WIRING SCHEMATIC DIRECT DRIVE...
Page 21: ...20 FIG 14 STANDARD WIRING SCHEMATIC A C READY DIRECT DRIVE...
Page 22: ...21 FIG 15 STANDARD WIRING SCHEMATIC BELT DRIVE...
Page 24: ...23 FIG 16 NH3 EXPLODED ASSEMBLY...