newins IC4800 Series Quick Start Manual Download Page 4

Before
510

After

510-10=500

-10

Compensated Value

   5. Wiring

       

    

1. 

Terminal wiring

    

* DC 24V Power (Option)
* Alarm Rating : AC 250V 2A(Resistance Load)

6

3

2

1

4

AC 

85~265V

N.O

N.C

AL1

COM

AL2

U(+)

V(-)

COM

2. A power source wiring

1. For an electric shock prevention to turn on electricity to the machinery and tools which 

after one sees a protective ground connection surely.

2. To the electric wire terminal to use the insulation sleeve compression terminal. 
3. The device's power supply voltage to match the voltage of the power is in check.
4.  For  the  protection  of  life  to  turn  on  an  electric  current  to  the  instrument  after 

attaching the cover.

Caution

1.  To  all  the  member  front  line  600V  vinyl  insulation  front  lines  (JIS  C3307),  or  to  use  the 

front line of above considerable width. 

2. To the  protective ground terminal to  connect above of 3rd  type(to  connect  below earth 

resistance 100Ω and smallest size 1.6㎜).

3.  Other  protection  devices  and  grounding,  the  grounding  in  public  may  be  affected  by 

noise. Accordingly the public are advised not to other devices. 

Attention

   6. Features

       

Multi-range input (T/C, RTD, Volt, mA)

High accuracy 16bit A/D converter

Peak hold function (Highest & Lowest)

Burnout function

2 points alarm & Dead band set

   

7.  Specifications

     

Input Type

Sensor  Type

Range

Scale

Symbol

TC

R(PR  13%)

0~1750

-

TC-R

K(CA)

-200~1350

-

TC-K

E(CRC)

-200.0~700.0

-

TC-E

J(IC)

-200.0~800.0

-

TC-J

T(CC)

-200.0~400.0

-

TC-T

PT

Pt100

-199.9~800.0

-

D-PT

JPt100

-199.9~500.0

-

J-PT

Measuring and display cycle : 100ms
Input resistance : Max 1MΩ
CMRR(Common Mode Rejection Ratio) : 140dB or more
NMRR(Normal Mode Rejection Ratio)   : 60dB or more
Moving average filter
Accuracy : ±0.2% FS
Alarm output : 2-SPDT, 1-SPDT

  Contact output type : Normal open, Normal close
  Max switching power : 60W 125VA
  Max switching voltage : DC 220V, AC 250V
  Max switching current : DC 2A, AC
  Max Carrying current : DC 3A, AC

Power supply

  Voltage : AC 110/220V(50~60Hz) DC 24V(Option)
  Power consumption : Max 4VA 
  Isolation resistance : 100MΩ , DC 500V
   (FG-Input, FG-Power, Power-Input, Input-Output)

Ambient temperature & Humidity

  Operation : -10~50℃, 10~90%
  Storage : -20~70℃, 5~95%

Material

  Case & Cover : ST 304
  Stem : ST 304, ST 306
  Socket  : ST 304, ST 306, ST 304L, ST 306L,
            Titanium, Monel, Hastelloy, Teflon Lining, Glass Lining

Dial Size : ¢100
Connection Size : PF 1/2"(STD)
Stem out dia : ¢3.2, ¢4.8, ¢6.4, ¢8.0mm
Enclose class : Drip proof
Cable Gland : PF 1/2"
Weight : 600g  
Mounting : Local mount

   8. 

Major  Functions

     

Sensor compensation function

  The  function  is  useful  for  compensating  error  by  long  sensor  line  or  changed  zero  point  by 

aged sensor.

   Ex) Before sensor adjust = 510℃
       After sensor adjust 
       = measured value + compensated value
       = 510 - 10 = 500℃

Alarm function 

  Alarm type : High, Low
  The alarm consists of 2 relays, and it can 
  output relay contact output individually.

  Ex) AL-1 : High alarm value 500.0, 
      AL-2 : Low alarm value 100.0, 
      Alarm dead band setting value 0.5
      The high  alarm(AL-1)  is  ON when  the  present  value(PV) is  500.0  or  more,  and  OFF  when 

499.5  or  less.  The  low  alarm(AL-2)  is  OFF  when  the  present  value(PV) is  100.5  or  more,  and 
ON when 100.0 or less.

Alarm 

ON

PV

500.0℃

Alarm 

OFF

High Alarm

499.5℃

Alarm 

ON

PV

100.5℃

Alarm 

OFF

100.0℃

Low  Alarm

MODE

MODE

MODE

A L 1mM

A L 2 M

A L D B

H

.

0 0 1 0

H

MODE

MODE

MODE