5. Wiring
1.
Terminal wiring
* DC 24V Power (Option)
* Alarm Rating : AC 250V 2A(Resistance Load)
6
3
2
1
4
AC
85~265V
N.O
N.C
AL1
COM
AL2
U(+)
V(-)
COM
2. A power source wiring
1. For an electric shock prevention to turn on electricity to the machinery and tools which
after one sees a protective ground connection surely.
2. To the electric wire terminal to use the insulation sleeve compression terminal.
3. The device's power supply voltage to match the voltage of the power is in check.
4. For the protection of life to turn on an electric current to the instrument after
attaching the cover.
Caution
1. To all the member front line 600V vinyl insulation front lines (JIS C3307), or to use the
front line of above considerable width.
2. To the protective ground terminal to connect above of 3rd type(to connect below earth
resistance 100Ω and smallest size 1.6㎜).
3. Other protection devices and grounding, the grounding in public may be affected by
noise. Accordingly the public are advised not to other devices.
Attention
6. Features
Multi-range input (T/C, RTD, Volt, mA)
High accuracy 16bit A/D converter
Peak hold function (Highest & Lowest)
Burnout function
2 points alarm & Dead band set
7. Specifications
Input Type
Sensor Type
Range
Scale
Symbol
TC
R(PR 13%)
0~1750
℃
-
TC-R
K(CA)
-200~1350
℃
-
TC-K
E(CRC)
-200.0~700.0
℃
-
TC-E
J(IC)
-200.0~800.0
℃
-
TC-J
T(CC)
-200.0~400.0
℃
-
TC-T
PT
Pt100
Ω
-199.9~800.0
℃
-
D-PT
JPt100
Ω
-199.9~500.0
℃
-
J-PT
Measuring and display cycle : 100ms
Input resistance : Max 1MΩ
CMRR(Common Mode Rejection Ratio) : 140dB or more
NMRR(Normal Mode Rejection Ratio) : 60dB or more
Moving average filter
Accuracy : ±0.2% FS
Alarm output : 2-SPDT, 1-SPDT
Contact output type : Normal open, Normal close
Max switching power : 60W 125VA
Max switching voltage : DC 220V, AC 250V
Max switching current : DC 2A, AC
Max Carrying current : DC 3A, AC
Power supply
Voltage : AC 110/220V(50~60Hz) DC 24V(Option)
Power consumption : Max 4VA
Isolation resistance : 100MΩ , DC 500V
(FG-Input, FG-Power, Power-Input, Input-Output)
Ambient temperature & Humidity
Operation : -10~50℃, 10~90%
Storage : -20~70℃, 5~95%
Material
Case & Cover : ST 304
Stem : ST 304, ST 306
Socket : ST 304, ST 306, ST 304L, ST 306L,
Titanium, Monel, Hastelloy, Teflon Lining, Glass Lining
Dial Size : ¢100
Connection Size : PF 1/2"(STD)
Stem out dia : ¢3.2, ¢4.8, ¢6.4, ¢8.0mm
Enclose class : Drip proof
Cable Gland : PF 1/2"
Weight : 600g
Mounting : Local mount
8.
Major Functions
Sensor compensation function
The function is useful for compensating error by long sensor line or changed zero point by
aged sensor.
Ex) Before sensor adjust = 510℃
After sensor adjust
= measured value + compensated value
= 510 - 10 = 500℃
Alarm function
Alarm type : High, Low
The alarm consists of 2 relays, and it can
output relay contact output individually.
Ex) AL-1 : High alarm value 500.0,
AL-2 : Low alarm value 100.0,
Alarm dead band setting value 0.5
The high alarm(AL-1) is ON when the present value(PV) is 500.0 or more, and OFF when
499.5 or less. The low alarm(AL-2) is OFF when the present value(PV) is 100.5 or more, and
ON when 100.0 or less.
Alarm
ON
PV
500.0℃
Alarm
OFF
High Alarm
499.5℃
Alarm
ON
PV
100.5℃
Alarm
OFF
100.0℃
Low Alarm
MODE
MODE
MODE
A L 1mM
A L 2 M
A L D B
H
.
0 0 1 0
H
MODE
MODE
MODE