Newasia NA8820 User Manual Download Page 3

 

3

F36 

Defrost stop mode 

0 or 1 

0:only controlled by time 
1:controlled by both time and 
temp 

F37 

Defrost heat mode 

0 or 1 

0: electric heat    1: hot gas 

F50 

External alarm mode 

0 -- 4 

0: without external alarm 
1: always open, unlocked 
2: always open, locked 
3: always closed, unlocked 
4: always closed, locked 

Alarm 

F59 

Whether use the evaporator 
sensor error alarm 

YES / NO 

YES 

 

F80 Password 

OFF 

0001 -- 9999 

OFF - 

OFF means no password 
0000 means clearing password 

System 

setting 

F81 Temperature 

unit 

C/F 

C:

 

Centigrade 

F: Fahrenheit 

F98 Reserved

 

 

Testing 

F99 Test 

self 

 

This function can attract all relays in turn, and please don’t use it 
when the controller is running! 

 End 

Exit 

 

 

7

 

Basic Operating Principle 

 Temperature controlling 

The controller has 2 temperature controlling mode: Refrigeration and Heat(F29).Temperature 

controlling point is controlled by “setting temperature (F11, or press the “set” key for some time to set)” 
and “temperature difference(F12)”.In refrigeration mode, the controller begins to refrigerate when the 
temperature of the temperature sensor is over “setting temperature 

  temperature difference”, and it stops 

refrigerating when the temperature is under “setting temperature 

  temperature difference”; In heat mode, 

the controller begins to heat when the temperature of the temperature sensor is under “setting temperature 

 temperature difference”, and it stops heating when the temperature is over “setting temperature 

 

temperature difference” 

 Compressor delay time 

The compressor delay time is set by F21, for example, 3 minutes. The controller contains a  

“compressor halt calculagraph”, and it begins to time when compressor stops, the program first check the 
calculagraph before booting the compressor next time, the program will immediately boot the compressor 
if the calculagraph reach 3 minutes ,if the calculagraph doesn’t reach 3 minutes ,it will boot again when the 
calculagraph reaches 3 minutes. Thus you can ensure that the boot alternation is over 3 minutes after halt, 
so it can prevent to breaking the compressor as a result of frequent boot. In addition, the controller doesn’t 
boot the compressor within 3 minutes after turning on the power supply, thus the compressor can also be 
protected in the state of power cut and then power on.

   

 Auto defrosting principle 

The controller has 3 defrost start modes which can be selected

F35

OFF: Defrost is off. 
1. Time alternation: the controller will start defrost according to the setting alternation time which can 

be set in “Defrost alternation time (F31)”.   

2. Accumulative compressor running time: if compressor accumulative running time reaches the time 

which set in “defrost alternation time (F31)”, the controller starts defrost.   

The controller has 2 defrost end modes which can be selected

F36

0: time control: the defrost time can be set by F33, the controller will stop defrosting when it reaches 

the defrost time. 

1: controlled by both time and temperature: the controller will check the defrost effect through 

evaporator sensor after starting defrost, If the sensor temperature reaches the “Defrost end temperature 
(F32)”, the controller will turn off defrosting, if the defrost time is longer than “defrost end time (F33)”, 
the defrosting will be turned off forcibly. 

You can select 2 defrost heat modes (F37): 
0: electric heat: the compressor stops and the defrost output is turned on (the defrost output controls 

the electric heater); 

1: hot gas: the compressor and defrost output is turned on (the defrost output controls the valve). 

 Dripping 

A dripping time can be set (F34). For example, set the dripping water with 5 minutes, after finishing 