NA8820 User Guide

 

 

3

 Main Function and Technique Index 

Main Function: 

)

 

Refrigeration Controlling (Refrigeration / heat): 

temperature display, temperature controlling 

(refrigeration/heat mode can be set)

compressor start delay protection, temperature sensor error alarm.   

)

 Defrost Controlling: 

2 defrost modes (electric heat, hot gas), 2 defrost start mode (time alternation, 

accumulative compressor running time), 2 defrost end mode (timing, controlled by both temperature and 
time) dripping, manual defrost, defrost sensor error alarm. 

)

 External alarm:

 one external alarm input, it can be set to 5 modes: always open, always open locked, 

always closed, always closed locked or forbidden. 

Main Technique Index: 

2

 Temperature display range: 

 -50

150

(The resolution is 0.1

                                                        -58

302

(The resolution is 0.1

2

 Power supply: 

  AC 220V±10% or AC 380V±10% 50Hz (Refer to the wiring diagram) 

2

 Operating environment: 

temperature -10

℃~

50

, humidity

85%. 

2

 Relay contact capability: 

  compressor 20A/250VAC, defrost 8A/250VAC (pure resistive load) 

2

 Temperature sensor: 

 NTC R25=5k

(25/50) 

=3470K 

 

     

2

 Executive standard: 

  Q/320585 XYK 01 (NA8820-CTDA) 

 

 

 

Operating Guide 

Panel: 

 

*

 

What’s the meaning of the index lights on the panel? 

The function of the LED on the panel is showing below: 

Index Light 

Name 

Light 

Flash 

 

Temp Setting

In the state of temp setting 

 

Refrigeration

Refrigerating 

Ready to refrigerate, in the state of compressor start delay 

protection 

 

Heat Heating 

Ready to heat, in the state of compressor start delay 

protection 

 

Defrost 

Defrosting 

Dripping or the state of compressor start delay protection

 

- - 

 

Alarm - 

Alarm 

state 

*

 

The meaning of the LED display 

      The LED usually shows temperature, if it shows “SHr”, it means the temperature sensor is short, 

and “OPE” means the temperature sensor is open. The temperature and the alarm code (Axx) will show 
alternately when in the alarm state. 

The code is showing below: 

Code Signification 

Explanation 

A11 

External alarm 

Alarm from external alarm signal, please refer to the internal parameter code “F50”

A21 

Temperature sensor error 

Open or short

showing “OPE” or “SHr”

 

A22 

Evaporator sensor error 

Open or short

showing “OPE” or “SHr” when press the key 

. If you don’t 

need to use the evaporator sensor, you can use the F59 to close the alarm. 

*

 

How to set the temperature? 

Press the key “set” for at least 2 seconds, then enter the state of temperature setting, here the LED 

displays the setting temperature, then using “

” key or “

” key can change the parameter

the 