background image

 

 

New Cosmos USA, Inc. 
Natural Gas Alarm  

806NIT

 

User’s Manual 

This manual has been prepared for the 806NIT Gas Alarm 
(“Gas Alarm”). If you have a Gas Alarm installed in your 
house or building, you should read and understand the 
important instructions and warnings contained in this 
manual and retain a copy for future reference. 

When natural gas, which consists primarily of methane, is 
present at concentrations of 10% or greater of the lower 
explosive limit (LEL) for methane, the Gas Alarm is 
designed to activate a gas leak alarm. The gas leak alarm 
consists of a flashing red LED light, an audible warning 
sound (a loud beep), and a recorded message.  

The Gas Alarm is equipped with an Itron Network Solutions 
(INS) communications module designed to automatically 
send information directly to your gas utility. including 
information associated with gas leak alarm activation, Gas 
Alarm error, low battery, and end-of-service-life.  

 

DANGER: EXPLOSION, FIRE AND 
ASPHYXIATION 

Natural gas leak alarm indicates an emergency 
situation and risk of explosion. 

 

EVACUATE IMMEDIATELY and take others with 
you. 

 

Do NOT use a phone, light a match, or turn on or 
off any light switches, flashlights, or appliances. 
Doing so could IGNITE a FIRE or EXPLOSION.

 

 

CALL 911 once you are safely outside the 
premises. 

 

Do NOT re-enter until told to do so by 
authorities.  

 

DANGER: ELECTROCUTION 

Do not subject the Gas Alarm to water or liquid by 
submerging it, spraying liquid on it or otherwise. 
Do not disassemble. 
 

 

 

DANGER: EXPLOSION 

This Gas Alarm is designed to act as a continuous 
monitor of natural gas that reaches the sensor.  
This Gas Alarm should not be used as a short-
term testing device to perform a onetime check  
for the presence of natural gas, as plugging the 
battery into the device in the presence of natural 
gas may cause an explosion.   

 

DANGER: FIRE AND EXPLOSION 

Improper disposal may result in fire or explosion. 
Contact your gas utility to arrange for disposal.   

 

DANGER: HAZARDOUS CONDITIONS 

Follow these instructions completely. Failure to  
do so may result in an undetected natural gas leak 
or other hazardous conditions that may cause 
serious injury or death. 

 

DANGER: HEARING DAMAGE 

Do not place your ear directly against or in close 
proximity to the Gas Alarm when it is alarming. 
Such exposure to the audible gas leak alarm may 
damage your hearing. 

 

WARNING 

 Do not change the Gas Alarm

’s installation position, 

relocate it from where it is installed, or tamper with the 
Gas Alarm or its battery. 

 Do not block, cover, obstruct or paint over the Gas Alarm 

or its sensor. The Gas Alarm can only detect natural gas 
that reaches its sensor.  

 Network or power outages may prevent your gas utility 

from receiving or processing automated notifications from 
your Gas Alarm, including notifications related to gas leak 
alarms.  Always follow these instructions, without relying 
on such automated notifications. 

 This Gas Alarm will reach its end-of-service-life in 

approximately 6 years from the date of installation. 
Contact your gas utility for replacement if you observe the 
end-of-service-life alarm indicator LED.  

 Do not modify, disassemble, submerge, strike, crush, or 

expose the Gas Alarm to high levels of volatile organic 
compounds. Doing so may cause the Gas Alarm to 
malfunction. 

 Commercially available batteries will not work with the 

Gas Alarm. Contact your gas utility to arrange for 
replacement.  

 Keep out of reach of children. 

 For indoor use only. 

 

NOTICE 

 The Gas Alarm must only be installed by your gas utility 

or an authorized gas utility contractor. 

 The Gas Alarm only detects natural gas. It does not 

detect carbon monoxide, fire, heat, smoke, flames, 
propane or any other gas. 

 The Gas Alarm is not a substitute for proper installation, 

use, and maintenance of natural gas appliances and 
piping systems. The Gas Alarm does not prevent natural 
gas leaks from occurring, nor can it eliminate any existing 
natural gas leaks or problems.  

General Description and Intended Use  

 

DANGER  

If you smell natural gas, evacuate the area 
immediately, then call 911.  Do not wait for the gas 
leak alarm to sound or for your gas utility to 
receive an automated notification. 

This Gas Alarm is designed to detect natural gas. Natural 
gas is a fossil fuel that is primarily made up of methane. It is 
commonly used for cooking, home heating and water 
heating. Natural gas is typically supplied through a gas 
main and utility service line connected to your home. 
Natural gas is odorless and colorless, but has a chemical 
odorant (mercaptan) add

ed to it to give it a distinct “rotten 

eggs” smell. Even odorized natural gas may not be 
detected by smell in an unoccupied space, by an individual 
with reduced sensitivity to smell, or in other situations.  

Natural gas is a highly flammable chemical compound. 
Although it happens rarely, a natural gas leak can occur 
inside a house or building. This can be dangerous because 
it increases risk of explosion and fire. The Gas Alarm is 
designed to activate a gas leak alarm when it detects 10% 
or greater of the LEL for methane, which is 0.5% or greater 
of methane in air. When the gas leak alarm activates, the 
Gas Alarm will 

beep 4 times and state “Danger – gas leak 

explosion risk 

– evacuate, then call 911.”  

In the event of a gas leak, you may smell natural gas before 
the gas leak alarm is activated. If you smell natural gas at 
any time, do not wait for the gas leak alarm to sound or 
check for Gas Alarm malfunction. Evacuate immediately, 

Summary of Contents for DeNova Detect 806NIT

Page 1: ...or Network or power outages may prevent your gas utility from receiving or processing automated notifications from your Gas Alarm including notifications related to gas leak alarms Always follow these instructions without relying on such automated notifications This Gas Alarm will reach its end of service life in approximately 6 years from the date of installation Contact your gas utility for repl...

Page 2: ...ully in the event that the natural gas leak alarm activates Never ignore any natural gas leak alarms EVACUATE IMMEDIATELY and take others with you Do NOT use a phone light a match or turn on or off any light switches flashlights or appliances Doing so could IGNITE a FIRE or EXPLOSION CALL 911 once you are safely outside the premises Do NOT re enter until told to do so by authorities DANGER EXPLOSI...

Page 3: ...sehold cleaning agents ammonia based cleaners paints varnishes aerosol sprays including compressed gas dusters or any other chemical on or near this Gas Alarm Specifications Contact Details New Cosmos USA Inc 650 Warrenville Rd Suite 101 Lisle IL 60532 Tel 847 749 3064 Conforming standards UL standard UL1484 FCC Certified Detection principle MEMS hot wire semiconductor sensor Target gas Methane ga...

Page 4: ...t mode and the green LED will flash 3 times per second for as long as you are in communications test mode Once in communications test mode press the test button additional times to test whether the detector is communicating normally with your gas utility s systems able to properly transmit detector error signals and able to properly transmit a low battery signal Success will be indicated as follow...

Page 5: ...ent battery needed After installing battery test the Gas Alarm following instructions in Troubleshooting Guide To reinstall the included battery or install a new battery you received from your gas utility Open the battery cover on the back of the detector This cover slides out of place To open place both thumbs on the back of the battery cover where the battery cover hooks snap into place Push dow...

Reviews: